ADDITIONAL CLEARANCES TO COMBUSTIBLES
Appliance Clearances
Unprotected Surfaces
Protected Surfaces (NFPA - 211)
Parallel
Corner
Parallel
Corner
Side
Rear
Side
Rear
No Heat Shields
16-in 12-in
12-in
7-in
6-in
6-in
405-mm 305-mm 305-mm
180-mm
150-mm
150-mm
Flue Collar and
14-in 6-in
10-in
7-in
6-in
6-in
Connector Shield
355-mm 150-mm 255-mm
180-mm 150-mm
150-mm
Double Wall Connector 14-in 6-in
10-in
7-in
6-in
6-in
355-mm 150-mm 255-mm
180-mm
150-mm
150-mm
Minimum alcove
58-in
40-in
Width
1475-mm
1015-mm
Maximum alcove
48-in
48-in
Width
1220-mm
1220-mm
Alcove Ceiling Above
34-in
12-in
Stove top
865-mm
305-mm
Hearth Mount
Side Trim
Top Trim Mantle
7-in
14-in
24-in
180-mm
355-mm 610-mm
Chimney Connector
Unprotected Surfaces (vert)
Protected Surfaces (vert).
No heat shields
12-in
6-in
305-mm
150-mm
Using Connector Shield
6-in
6-in
150-mm
150-mm
Double Wall Connector
6-in
6-in
150-mm
150-mm
Unprotected Surfaces (horiz.)
Protected Surfaces (horiz.)
Single Wall Connector
18-in
12-in
460-mm
305-mm
Double Wall Connector
6-in
6-in
150-mm
150-mm
FLOORING REQUIREMENTS
The unit must be placed on non-combustible material extending 2-in (50mm) beyond each side, 2-in (50mm)
beyond the rear, and 2-in (50mm) beyond each side of the chimney connector. If the optional side fuelling
door is used, the floor protection must extend 16-in (410mm) beyond the door. Combustible flooring 16-in
(410mm) beyond the front and 8-in (200mm) beyond each side of the front fuel opening must be protected
by either a listed non-combustible insulative floor protector or a field installed non-combustible insulative floor
protection with an R value of at least 1.2.
For use in Canada, the non-combustible floor protection must be extended to 18-in (460mm) beyond the fire
door(s) and 8-in (200mm) beyond the sides and rear of the stove.