background image

MASONRY FIRE PLACE

Before the installation the entire fireplace system should
be inspected for condition and code compliance prior to
connecting to the fireplace chimney.  Older fireplaces and
chimneys may not have been constructed to current-day
codes.

The fireplace and chimney should be in, or bought up to
acceptable condition and proper clearances should be
met before connecting to the fireplace chimney.

The size of the flue must be considered.  If the fireplace
chimney is too large, a relining system may be installed
using an approved relining system.

Connection to a masonry chimney may be done by
breaching into the chimney from the front of the fireplace,
no less than 8” above the bottom of the first flue tile, by
installing a stainless steel or other listed chimney con-
nector from the appliance flue outlet up through the fire-
place damper and smoke chamber, terminating at the first
flue tile, or by installing a stainless steel or other listed
relining system from the flue outlet up the entire length of
the chimney, where necessary.

5

Fig.7

or back drafts occur whether or not there is com-
bustion present.

2.

Existing fuel-fired equipment in the house, such 
as fireplaces or other heating appliances, smell, 
do not operate properly, suffer smoke roll-out 
when opened, or back-draft whether or not there
is combustion present.

3.

Opening a window slightly on a calm (windless) 
day alleviates any of the above symptoms.

4.

The house is equipped with a well-sealed 
vapour barrier and tight fitting windows and/or 
has any powered devices that exhaust house air.
(e.g. extraction hoods or tumble dryers)

5.

There is excessive condensation on windows in 
the winter.

6.

A ventilation system is installed in the house.

If these or other indications suggest that infiltration air is
inadequate, additional combustion air should be provided
from the outdoors.  Outside combustion air can be pro-
vided to the appliance by the following means:

1.

Indirect method:  for an appliance not certified for
direct connection of outside combustion air, the 
outside air is ducted to a point no closer than 
(12”) 300mm from the appliance, to avoid affect-
ing the performance of the appliance.

2.

A mechanical ventilation system:  if the house 
has a ventilation system (air change or heat 
recovery):
a.  The ventilation system may be able to provide
sufficient combustion make-up air for the solid-
fuel-fired appliance.
b.  The householder should be informed that the
ventilation system might need to be re-balanced 
by a ventilation technician after installation of the
appliance.

VENTILATION & COMBUSTION AIR
REQUIREMENTS

Ventilation and an adequate air supply is necessary to
supply combustion air to the appliance.  Refer to your
Local Authority for current requirements in your jurisdic-
tion.

Outside combustion air may be required if:

1.

The solid-fuel-fired appliance does not draw 
steadily, smoke rollout occurs, fuels burns poorly, 

SPILLAGE TEST

In all installations a spillage test should be carried
out to ensure there is sufficient combustion air and
the flue system is 
1.

Light/burn appliance under normal condi-
tions in accordance with this installation 
manual.

2.

Close all doors and windows.

3.

Operate all appliances requiring air at full 
rate (eg. extraction hoods, tumble dryers 
etc).

4.

Check for spillage.

LOCATION:

There are several conditions in selecting a LOCATION for
your 104 MK II.  These are:-

a.

Distance from a suitable safe chimney (see 
chimneys).

Содержание 104 MK II

Страница 1: ...IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOLLOW THE INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION IN YOUR AREA THIS STOVE MUST BE CONNECTED TO A LISTED HIGH TEMPERATURE RESIDENTIAL TYPE AND BUILDING HEAT ING APPLIANCE CHIMNEY OR AN APPROVED MASONRY CHIMNEY WITH FLUE LINER MANUFACTURED BY WATERFORD STANLEY MARKETING LIM...

Страница 2: ...dards and Local Codes It should be noted that the requirements and these publications may be superseded during the life of this manual The chimney must have a CROSS SECTIONAL AREA of at least 182 39 sq cm 28 27 square inches It is best to connect to a chimney of the same size as connection to a larger size may result in somewhat less draught DO NOT CONNECT TO A CHIMNEY SERVING ANOTHER APPLIANCE Mi...

Страница 3: ...a masonry chimney must extend through the wall to the inner face or liner but not beyond and must be firmly cemented to masonry The connector may pass through walls or partitions con structed of combustible material to a masonry chimney provided the connector system selected is installed in accordance with the proper clearances and conditions See figures 2 3 4 5 6 pages 3 4 THIMBLES Thimbles for c...

Страница 4: ...tric with and spaced 1 25mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimney section supported on both sides with sheet steel supports of min 24 gauge thickness Supports should be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney sec tion Fasteners used to secure chimney sections...

Страница 5: ...here is excessive condensation on windows in the winter 6 A ventilation system is installed in the house If these or other indications suggest that infiltration air is inadequate additional combustion air should be provided from the outdoors Outside combustion air can be pro vided to the appliance by the following means 1 Indirect method for an appliance not certified for direct connection of outs...

Страница 6: ...chimney connector and clean the sections Replace cor roded pipe sections The fitting of a slip joint in the stove pipe makes the dismantling easy for cleaning and inspec tion of chimney and stove When inspecting a masonry chimney start at the clean out door normally found in the basement at the base of the chimney or on the outside If the chimney does not have a clean out door it must be inspected...

Страница 7: ...Bottom of Top Baffle Assembly 13 Back Baffle 14 Back Panel 16 Hob 17 Hot Plate 18 Spigot 19 Flue Increaser 20 Door Knob 21 Door Catch 22 Rear Side Brick 23 Air Baffle 24 Top of Top Baffle Assembly 25 Front Fire Fence 26 Bottom Brick 27 Optional heat Shield 28 Optional Flue Heat Shield 29 Blanking Plate Back Outlet 30 Door Hinge Pin 31 Spacer Top Baffle to Hob 28 ...

Страница 8: ...rom the chimney connec tor Double wall chimney connectors may be substituted for the Shielded Pipe provided it is listed for a 10 250mm clearance or less WALL PROTECTORS Materials and products listed for the purpose of reducing clearance to combustibles shall be installed in accor dance with the conditions of the listing and the clearances may be reduced by the percentage reduction as stated in th...

Страница 9: ...ORY TO CURE WELL AND TO SEASON THE STOVE CAUTION NEVER USE GASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IT IS IN USE DO NOT USE GRATE OR ELEVATE FIRE BUILD WOOD FIRE DIRECTLY ON HEARTH OPERATE STOVE ONLY WITH FUELLING DOOR CLOSED BURN WOOD ONLY LIGHTING 1 Lay...

Страница 10: ...roduces tar and other organic vapours which combine with expelled moisture to form creosote The creosote vapours condense in the rela tively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote makes and extremely hot fire The chimney connector and chimney should be inspect ed at least twice monthly during the heating seaso...

Страница 11: ...12 Waterford Stanley Bilberry Waterford Ireland Telephone 051 302300 Facsimile 051 302375 Rev 005 DP 020625 ...

Отзывы: