REDUCED CLEARANCES
All the figures shown are for clearance to combustibles,
which can be reduced if an approved wall protection sys-
tem or non-combustible walls are used. When the 104
MKII Listed Room Heater Part, item number 27, Stove
Shield is used, together with a Listed Pipe Shield the
clearances may be reduced to 9 “ (229mm) from the
stove back and 10 “ (250mm) from the chimney connec-
tor. Double wall chimney connectors may be substituted
for the Shielded Pipe provided it is listed for a 10 “
(250mm) clearance or less.
WALL PROTECTORS
Materials and products listed for the purpose of reducing
clearance to combustibles shall be installed in accor-
dance with the conditions of the listing and the clearances
may be reduced by the percentage reduction as stated in
the wall shield manufacturer’s instructions.
For clearance reduction systems using an air space
between the combustible wall and the wall protector,