background image

104 - MKII 

PRE-INSTALLATION ASSEMBLY

Step 1:

After removing the stove from the pack, open the fire door
and remove packed contents from the Firebox.  Empty
the Jiffy Bag.

Step 2:

Lay the stove on its side.  Insert and secure a leg in the
recess at each corner of the base using 25mm x 6mm (1
in. x 1/4 in.)  flat head screws and 6mm (1/4 in.) flat wash-
ers.

Step 3:

Carefully stand the unit upright on its legs.

Step 4:

Remove the nut and washer from the knob.  Place in posi-
tion, insert the screw in position with spring washer and
nut provided.  See Sketch.

104 MK II

GENERAL INSTRUCTIONS

BUILDING CODES

Consult the LOCAL BUILDING CODE in all cases as to
the particular requirements concerning the installation of
SOLID FUEL TYPE ROOM HEATERS.  This 104 MK II
WOOD BURNING STOVE is intended to be installed in
accordance with National Fire Protection Associations
Standard for Chimneys, Fireplaces and Vents, NFPA 211-
1977.

This stove has been tested and listed by UNDERWRIT-
ERS LABORATORIES INC, and as such carries the U.L.
and U.L.C. LABEL.  All building codes which recognise
the value of U.L. Listing will accept applications for and
approve installations of this product.

INSTALLATION INSTRUCTIONS

MUST BE FOLLOWED.

CHIMNEYS

The 104 MK II Wood Stove is a Radiant Room Heater and
must be connected to a CHIMNEY of the proper size and
type.

The complete installation must be done in accordance
with current Standards and Local Codes.  It should be
noted that the requirements and these publications may
be superseded during the life of this manual.

The chimney must have a CROSS-SECTIONAL AREA of
at least 182.39 sq. cm. (28.27 square inches).  It is best
to connect to a chimney of the same size, as connection
to a larger size may result in somewhat less draught.  

DO

NOT CONNECT TO A CHIMNEY SERVING ANOTHER
APPLIANCE.  

Minimum chimney height 4.57 meters (15

ft.) from floor on which stove is installed.  An existing
masonry chimney should be inspected, and, if necessary,
repaired by a competent mason or relined, using an
approved relining system.

DO NOT CONNECT TO OR USE IN CONJUNCTION
WITH ANY AIR DISTRIBUTION DUCTWORK UNLESS
SPECIFICALLY APPROVED FOR SUCH INSTALLA-
TION.

Note:

Connection to type “B” Gas Vents, approved for

connection to a certain gas burning appliance only, will
result in a fire.

CHIMNEY TYPES - USA ONLY

The stove must be connected to a U.L. 103 Listed
Residential type H.T. and Building Heating Appliance.
Chimney installed in accordance with the manufacturers
instructions or a masonry chimney constructed in accor-
dance with NFPA 211 Chimney vents and Solid Fuel
Burning Appliances.

2

Step 5:

Take the hotplate (WIF 008) and place it in the large
opening on the top.  Do not remove the Hot Plate when
the unit is in operation.  Remove only for cleaning.

Step 6:

Attach the Spigot, item number 18, in the exploded view
to the hob, item number 16 using the two 1/4” (6mm)
counter sunk screws provided.

Check that all parts are securely fitted before firing the
unit.

The stove is now ready for installation.

Fig.1

Содержание 104 MK II

Страница 1: ...IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOLLOW THE INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION IN YOUR AREA THIS STOVE MUST BE CONNECTED TO A LISTED HIGH TEMPERATURE RESIDENTIAL TYPE AND BUILDING HEAT ING APPLIANCE CHIMNEY OR AN APPROVED MASONRY CHIMNEY WITH FLUE LINER MANUFACTURED BY WATERFORD STANLEY MARKETING LIM...

Страница 2: ...dards and Local Codes It should be noted that the requirements and these publications may be superseded during the life of this manual The chimney must have a CROSS SECTIONAL AREA of at least 182 39 sq cm 28 27 square inches It is best to connect to a chimney of the same size as connection to a larger size may result in somewhat less draught DO NOT CONNECT TO A CHIMNEY SERVING ANOTHER APPLIANCE Mi...

Страница 3: ...a masonry chimney must extend through the wall to the inner face or liner but not beyond and must be firmly cemented to masonry The connector may pass through walls or partitions con structed of combustible material to a masonry chimney provided the connector system selected is installed in accordance with the proper clearances and conditions See figures 2 3 4 5 6 pages 3 4 THIMBLES Thimbles for c...

Страница 4: ...tric with and spaced 1 25mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimney section supported on both sides with sheet steel supports of min 24 gauge thickness Supports should be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney sec tion Fasteners used to secure chimney sections...

Страница 5: ...here is excessive condensation on windows in the winter 6 A ventilation system is installed in the house If these or other indications suggest that infiltration air is inadequate additional combustion air should be provided from the outdoors Outside combustion air can be pro vided to the appliance by the following means 1 Indirect method for an appliance not certified for direct connection of outs...

Страница 6: ...chimney connector and clean the sections Replace cor roded pipe sections The fitting of a slip joint in the stove pipe makes the dismantling easy for cleaning and inspec tion of chimney and stove When inspecting a masonry chimney start at the clean out door normally found in the basement at the base of the chimney or on the outside If the chimney does not have a clean out door it must be inspected...

Страница 7: ...Bottom of Top Baffle Assembly 13 Back Baffle 14 Back Panel 16 Hob 17 Hot Plate 18 Spigot 19 Flue Increaser 20 Door Knob 21 Door Catch 22 Rear Side Brick 23 Air Baffle 24 Top of Top Baffle Assembly 25 Front Fire Fence 26 Bottom Brick 27 Optional heat Shield 28 Optional Flue Heat Shield 29 Blanking Plate Back Outlet 30 Door Hinge Pin 31 Spacer Top Baffle to Hob 28 ...

Страница 8: ...rom the chimney connec tor Double wall chimney connectors may be substituted for the Shielded Pipe provided it is listed for a 10 250mm clearance or less WALL PROTECTORS Materials and products listed for the purpose of reducing clearance to combustibles shall be installed in accor dance with the conditions of the listing and the clearances may be reduced by the percentage reduction as stated in th...

Страница 9: ...ORY TO CURE WELL AND TO SEASON THE STOVE CAUTION NEVER USE GASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IT IS IN USE DO NOT USE GRATE OR ELEVATE FIRE BUILD WOOD FIRE DIRECTLY ON HEARTH OPERATE STOVE ONLY WITH FUELLING DOOR CLOSED BURN WOOD ONLY LIGHTING 1 Lay...

Страница 10: ...roduces tar and other organic vapours which combine with expelled moisture to form creosote The creosote vapours condense in the rela tively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When ignited this creosote makes and extremely hot fire The chimney connector and chimney should be inspect ed at least twice monthly during the heating seaso...

Страница 11: ...12 Waterford Stanley Bilberry Waterford Ireland Telephone 051 302300 Facsimile 051 302375 Rev 005 DP 020625 ...

Отзывы: