I pg 34

Pool Heat Pump

Code

Action

EE 01

High-pressure Failure

EE 02

Low-pressure Failure

EE 03

Water Flow Failure

EE 04

Heating Water Temperature Overheating Failure

EE 05

Exhaust Temperature Failure

EE 06

Wired Controller EEPROM Data Read/Write Failure

EE 07

Converter Board EEPROM Data Read/Write Failure

EE 08

Wired Controller and Converter Board Communication Failure

EE 09

Converter Board and Outdoor Board Communication Failure

EE 10

Outdoor Board and Module Board Communication Failure 

EE 11

Module Board Failure

EE 12

DC Bus Overvoltage, Low-Voltage Protection

EE 13

Overcurrent Protection

EE 31

Outdoor DC Fan Failure (only for DC Fan Model)

PP 01

Inlet Water Temperature Sensor Failure

PP 02

Outlet Water Temperature Sensor Failure

PP 03

Outdoor Coil Sensor Failure

PP 04

Return Air Sensor Failure 

PP 05

Outdoor Environment Sensor Failure

PP 06

Compressor Exhaust Sensor Failure

PP 07

Winter Antifreeze Protection

PP 08

Low Ambient Temperature Protection

PP 09

Heating Ambient Temperature Overheating Protection

PP 10

Cooling Outer Coil Overheating Protection

Defrosting

Defrosting Indicator Heating Icon Flash Prompt

Code

Problem - Action / Remedy

HP, HP3

Action / Remedy:

 

Make sure the water reaches the pool heat 

pump and the pool pump is completely filled to the rim. Otherwise:
- Fill the pool pump with water, and check to see if the pipes 

between the pool pump and the pool are watertight (there should 

be no air intake);

- Check the swimming pool and pool skimmer baskets and the drain 

at the bottom of the pool for obstructions;

- Check the filter cartridges for obstructions (wash or change the

cartridges, as the case may be);

- Insure that the bypass valves are in the correct positions so that

the water flows adequately;

- Backwash sand filter (insure that there is a sufficient amount of 

sand and verify that it does not have to be changed. Consult a 

swimming pool specialist if necessary);

- Make sure the vacuum robot is disconnected so that the water

flows freely.

OFF

Problem: 

The desired water temperature setting programmed 

is below 60°F (15°C) for the Multi function electronic control 

OR the electronic control with diagnostics is OFF or could be 

defective.

Action / Remedy: 

Reprogram the desired water temperature 

setting to a higher setting for the electronic control with Multi 

Function. For the electronic control with diagnostics and the 

reversible electronic control with diagnostics (XLR), press on key 

¨ON/OFF¨.

PSD, oC1 &

Sc1

Problem: 

The water temperature probe has a loose connection 

or is faulty. The probe will need to be checked and replaced if 

required.

Action / Remedy:

 Contact customer service.

ot

Problem:

 Water temperature is higher than 45°C (113°F) within 

the unit (this code is only displayed on the electronic control with 

diagnostics).

Action / Remedy:

- Make sure the bypass valves are in the correct positions;
- Proceed to the calibration of the electronic control with diagnotics 

and reversible electronic control with diagnostics (XLR).

Service Analyser Codes (Inverter Models)

Содержание ElectroHeat MKIV

Страница 1: ...lation and Operation Manual Manuel d installation et d utilisation This equipment must be installed and serviced by a qualified technician Improper installation can create electrical hazards which cou...

Страница 2: ...er wire as sized to comply with current Standards and local statutory authorities in relation to the circuit conductors supplying the equipment A cable connector is provided on this unit to connect a...

Страница 3: ...osts and size of the unit required Pools not covered with a solar blanket lose 2 to 3 times more heat regardless of types of heating Record your model s information Keep this manual and your original...

Страница 4: ...ided and will greatly reduce unit s heating capacity and efficiency The unit should be located as close as practically possible to the existing pool pump and filter to minimize water piping The use of...

Страница 5: ...3 Units which are installed more than 1 metre below water level will require a flocheck valve to be fitted to prevent the heat pump from cycling when no water flow is detected 4 For units installed ab...

Страница 6: ...s the metal framework of the pool the light the pump the filter if metal the pool heat pump any automatic chlorine generator and any other metal or electrical equipment bonded to your pool On some old...

Страница 7: ...105 C 5 Close control box cover 6 Re install the access panel To control heaters that are operated in parallel connect wiring at same locations on heater Control It is imperative that each control cir...

Страница 8: ...nditions air temperature will be warmer during day time hours To accelerate the initial heating period owners may opt to increase the ambient air temperature artificially around the evaporator area of...

Страница 9: ...ettings To program the desired water temperature press BOTH the UP and DOWN arrow keys at the same time until the temperature degree displays change degree then release them Press the UP arrow or DOWN...

Страница 10: ...the SET key until F C appears on the temperature display 2 Whilst F C is still on the display Press and release the UP or DOWN arrow key until C is displayed 3 Release all keys and the control will no...

Страница 11: ...gs menu and set the off timer to switch the unit off automatically 4 The timer function may repeat and is only deactivated when the ON OFF button is selected 5 Timer error is less than 1min h Note Tim...

Страница 12: ...d maintenance For Waterco pool heat pumps located within one kilometre from the coast a coating must be applied to the unit prior to site delivery on the evaporator fins and exposed metal surfaces to...

Страница 13: ...it is mandatory that the water accumulated in the pool heat pump be drained completely before freezing weather prevails Improper winterizing may damage the pool heat pump and will void the warranty T...

Страница 14: ...dried open the water IN and water OUT valves on the pool heat pump 6 Close the bypass valve to allow full water flow through the pool heat pump If water is now seen running from the outside of the po...

Страница 15: ...off early 2 If you have installed a timer or the pool heat pump is equipped with an integrated timer be sure it is programmed to allow the pool pump to work for sufficient time in order to reach the...

Страница 16: ...y Ensure vacuum robot or other cleaners are disconnected so that the water flows freely Check that there are no leaks on the pool plumbing there should be no air leaks in the pipework Service Analyser...

Страница 17: ...and electronic control with diagnostics I pg 32 Pool Heat Pump Code Problem Action Remedy FS DEF FS4 Problem Normal defrost cycle The fan blades are turning but the compressor has stopped For Electro...

Страница 18: ...watertight there should be no air intake Check the swimming pool and pool skimmer baskets and the drain at the bottom of the pool for obstructions Check the filter cartridges for obstructions wash or...

Страница 19: ...panel please advise the Waterco service agent There are no other warranties express or implied including but not limited to implied warranties of merchantability or fitness for a particular purpose Du...

Страница 20: ...nnecter un conducteur en cuivre de taille appropri e entre cet appareil et tout quipement m tallique bo tiers m talliques d quipement lectrique tuyau d eau m tallique ou tout conduit 1 5 m de l appare...

Страница 21: ...ts d exploitation et la taille de l appareil requis Les piscines non recouvertes d une toile solaire perdent 2 3 fois plus de chaleur quel que soit le type de chauffage Enregistrez votre mod le d inf...

Страница 22: ...pareil L appareil doit tre situ le plus pr s possible de la thermopompe et du filtre de la piscine en place pour minimiser la fuite d eau L utilisation de coudes 90 degr s et de coudes rayon court dan...

Страница 23: ...l eau n cessitent l installation d une valve de v rification de d bit pour emp cher la thermopompe de se d clencher si aucun d bit d eau n est d tect 4 Pour les appareils install s au dessus du niveau...

Страница 24: ...n rateur automatique de chlore et tout autre quipement m tallique ou lectrique coll votre piscine Sur certaines piscines plus anciennes ce fil de liaison de sous structure peut ne pas exister Dans ce...

Страница 25: ...ture d au moins 105 C 5 Fermez le couvercle du bo tier de commande 6 R installer le panneau d acc s Pour contr ler les appareils de chauffage qui fonctionnent en parall le branchez le c blage aux m me...

Страница 26: ...ons atmosph riques temp rature d air seront plus chaudes pendant la journ e Pour acc l rer la p riode de chauffage initial les propri taires peuvent prendre pour augmenter la temp rature de l air ambi...

Страница 27: ...er Et R gler Les Param tres De Temp rature Pour programmer la temp rature de l eau d sir e appuyez simultan ment sur les touches HAUT et BAS en m me temps jusqu ce que le degr de temp rature affich e...

Страница 28: ...ours indiqu sur l cran Appuyez sur la touche HAUT ou BAS jusqu ce que C soit affich 3 Rel cher toutes les touches et le panneau va maintenant tre configur pour Celcius N appuyez pas sur tous les autre...

Страница 29: ...z dans le menu R glages et allumez un chronom tre pour allumer l appareil automatiquement 3 Pour Arr ter la fonction chronom tre lorsque la thermopompe est activ e entrez dans le menu R glages et arr...

Страница 30: ...emplacement de la machine par rapport l eau sal e et l entretien Pour les thermopompes chauffage Waterco situ s moins d un kilom tre de la c te un enrobage doit tre appliqu avant leur livraison sur le...

Страница 31: ...t obligatoire que l eau accumul e dans la Thermopompe soit drain e compl tement avant que la cong lation a lieu Une proc dure d hivernage d fectueuse peut endommager la Thermopompe et annulera la gara...

Страница 32: ...un d bit d eau travers la thermopompe de chauffage Si l eau est maintenant vu l ex cution de l ext rieur de la Thermopompe ou l int rieur de la Thermopompe apr s une courte p riode de temps vous devez...

Страница 33: ...Thermopompe est quip e d un chronom tre int gr V rifier qu il est programm pour permettre la thermopompe de la piscine de travailler pendant un temps suffisant afin d atteindre la temp rature programm...

Страница 34: ...aspirateur automatique ou d autres appareils de nettoyage sont d connect s de sorte que l eau s coule librement V rifier qu il n y a pas de fuite dans la tuyauterie de la piscine il ne devrait pas y...

Страница 35: ...robl me d action Solution FS DEF FS4 Probl me Le cycle normal de d givrage Les pales du ventilateur tournent mais le compresseur s arr te Pour les mod les Chaleur lectrique Ultra et r versible les pal...

Страница 36: ...a piscine avec de l eau de la thermopompe V rifier si les tuyaux entre la thermopompe et la pompe de la piscine sont tanches il ne devrait pas y avoir de prise d air Examiner la piscine et l cumoire d...

Страница 37: ...icites de qualit marchande ou d ad quation un usage particulier Pendant la p riode de garantie Waterco r parera ou remplacera sa discr tion sans frais tout produit ou pi ce jug d fectueux dans des con...

Отзывы: