WS1HR & WS1.25HR Manual
Page 21
Step 8F – Set Regeneration Time Options using the
▼
or
▲
button. If value is set to:
• “NORMAL” means regeneration will occur at the preset time;
• “on 0” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or
• “ on 0” means regeneration will occur at one of the following:
— the preset time when the gallons capacity falls below the reserve or the specifi ed number of days
between regenerations is reached whichever comes fi rst;
or
— after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
See Table 9 for more detail. Press NEXT to go to Step 9F. Press REGEN to return to previous step.
STEP 8F
Step 7F – Set Volume Capacity using the
▼
or
▲
button. If value is set to:
• “oFF” regeneration will be based solely on the day override set (see Installer Display/Settings Step 3I);
or
• as a number regeneration will be based off the value specifi ed.
See Table 9 for more detail. Press NEXT to go to Step 8F. Press REGEN to return to previous step.
STEP 7F
Step 12F: Set the Service Call Indicator by using the
▲
or
▼
buttons.
Range is in ¼ of a year increments from 0.25 to 9.75 years. Selecting
OFF will disable this feature. Press NEXT to exit OEM Filter System
Setup. Press REGEN to return to previous step.
STEP 12F
RETURN TO NORMAL MODE
Step 9F: Set Relay operation using the
▲
or
▼
button. The choices are:
• Set Time on: Relay activates after a set time at the beginning of a regeneration and then deactivates
after a set period of time. The start of regeneration is defi ned as the fi rst backwash cycle or Dn brine
cycle, which ever comes fi rst.
• Set Gal Softening on: Relay activates after a set number of gallons have been used while in service
and then deactivates after a set period of time or after the meter stops registering fl ow, whichever
comes fi rst.
• Set Gal Softening Regen on: Relay activates after a set number of gallons have been used while in
service or during regeneration and then deactivates after a set period of time or after the meter stops
registering fl ow, which ever comes fi rst.
• Off: If set to Off, Steps 10F and 11F will not be shown.
Press NEXT to go to Step 10F. Press REGEN to return to previous step.
STEP 9F
STEP 10F
Step 10F: Set Relay Actuation Time or Gallons using the
▲
or
▼
buttons. The choices are:
• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior to
activating the relay. The start of regeneration is defi ned as the fi rst backwash cycle or Dn brine cycle,
which ever comes fi rst. Ranges from 1 second to 200 minutes.
•Relay Actuation Gallons: Relay activates after a set number of gallons have passed. Ranges from 1 to
50 gallons.
Press NEXT to go to Step 11F. Press REGEN to return to previous step.
STEP 11F
Step 11F: Set Relay Deactivate Time using the
▲
or
▼
buttons.
• If Set Time on is selected in Step 9F the relay will deactivate after the time set has expired. Ranges
from 1 second to 200 minutes.
• If Set Gal Softening on or Set Gal Softening Regen on is selected in Step 9F the relay will deactivate
after the time set has expired or after the meter stops registering fl ow, whichever comes fi rst. Ranges
from 1 second to 20 minutes.
Press NEXT to go to Step 12F. Press REGEN to return to previous step.
Содержание WS1.25HR
Страница 2: ......
Страница 13: ...WS1HR WS1 25HR Manual Page 13 Figure 3 Figure 4 Figure 1 Figure 2...
Страница 30: ...Page 30 WS1HR WS1 25HR Manual Drawings and Part Numbers...
Страница 42: ...Page 42 WS1HR WS1 25HR Manual Flow Diagrams Service and Backwash...
Страница 43: ...WS1HR WS1 25HR Manual Page 43 Flow Diagrams Downflow and Upflow WS1HR Only...
Страница 44: ...Page 44 WS1HR WS1 25HR Manual Flow Diagrams Rinse and Fill...
Страница 54: ...Page 54 WS1HR WS1 25HR Manual...
Страница 55: ...WS1HR WS1 25HR Manual Page 55...
Страница 56: ...Page 56 WS1HR WS1 25HR Manual...
Страница 57: ...WS1HR WS1 25HR Manual Page 57...
Страница 58: ...Page 58 WS1HR WS1 25HR Manual...
Страница 59: ...WS1HR WS1 25HR Manual Page 59...