CK and EQ Manual

Once the OEM Cycle Sequence has been set, the other procedures can be accessed in any order. Details on each of the procedures 

are provided on the following pages. 

To “lock out” access to diagnostic and valve history displays and modifications to settings except hardness, day override, time 

of regeneration and time of day by anyone but the manufacturer, press 

, NEXT, 

, and CLOCK in sequence after settings are 

made. To “unlock”, so other displays can be viewed and changes can be made, press 

, NEXT, 

, and CLOCK in sequence.

When in operation normal user displays such as time of day, volume remaining before regeneration, present flow rate or days 

remaining before regeneration are shown. When stepping through a procedure, if no buttons are pressed within five minutes, the 

display returns to a normal user display. Any changes made prior to the five minute time out are incorporated.

To quickly exit OEM Softener Setup, OEM Filter Setup, Installer Display Settings, Diagnostics or Valve History press CLOCK. 

Any changes made prior to the exit are incorporated. 

When desired, all programming and information in Diagnostics may be reset to defaults when the valve is installed 

in a new location. To reset, press NEXT and 

 simultaneously to go to the Softening/Filtering screen. Press 

 and 

 

simultaneously to reset programming and diagnostic values. Screen will return to User Display.

Sometimes it is desirable to have the valve initiate and complete two regenerations within 24 hours and then return to the preset 

regeneration procedure. It is possible to do a double regeneration if the control valve is set to “DELAYED REGEN” or “BOTH” 

in OEM Softener System Setup or OEM Filter System Setup. To do a double regeneration:

1. Press the “REGEN” button once. REGEN TODAY will flash on the display.

2. Press and hold the “REGEN” button for three seconds until the valve regeneration initiates.

Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the preset regeneration time. 

For Valve Type 1.0T, press and hold CLOCK and 

 for about 3 seconds to initiate an exchange of the tank in Service without 

cycling the regeneration valve. After tank switch, days remaining and capacity remaining status is retained for each tank until the 

next regeneration.

Prior to selecting the upflow regeneration cycle, verify that the correct body, main piston, regenerant piston and stack are being 

used, and that the injector plug(s) are in the correct location. Refer to the Service Manual for drawings and part numbers.

Proportional Brining

If the system is set up as a prefill upflow softener the control valve can also be set to normal or proportional brining.

This step will appear after Step 7S and before Step 8S if the system is set up as a prefill 

upflow softener. The following options can be selected:

• NORMAL FILL - System always prefills with the salt level selected. 

• PROPORTIONAL FILL - If proportional brining is selected, the actual salt fill time will 

be calculated by dividing the actual volume of treated water used by the full volumetric 

capacity, then multiplying this value by the maximum salt fill time.

Press NEXT to go to the next step. Press REGEN to return to the previous step.

Backlight Control

As an energy-saving feature, the control will automatically turn off the display illumination after 5 minutes of inactivity.  Any 

further keypad activity will temporarily re-illuminate the display for 5 minutes. The Energy Saver feature default is ON.

The Master Illumination button is located in the lower right hand portion of the board.  The purpose of the button is to manage 

the keypad backlights and the Energy Saver feature.  When the keypad backlights are OFF, pressing and holding this button for 

about 5 seconds will turn the lights ON, and turn the energy-saver feature OFF, which will be indicated with a display “ENERGY 

SAVER OFF”.  If the button is not held until the Energy Saver Off display is shown, the backlights for the display and the 

keypad will both go OFF after 5 minutes of no keypad activity.  (The keypad backlights will remain OFF until either the Master 

Illumination or any keypad button is pressed to turn them back ON.)

Содержание CK

Страница 1: ...Water Specialist CK and EQ Control Valve Programming and Cover Drawing Manual...

Страница 2: ...Page 2 CK and EQ Manual...

Страница 3: ...ver and Drive Assembly 4 OEM General Programming Instructions 5 OEM Cycle Sequence 7 OEM Softener System Setup 13 Setting Options Table 16 OEM Filter System Setup 17 Installer Display Settings 20 User...

Страница 4: ...ect On Off Operation PC Board Relay Terminal Block Relay RLY 1 Coil V Coil RLY 2 Coil Relay Driver Output Type Dual Solid State 12VDC wet contacts N O Relay Driver Output Capacity 12VDC 100mA per rela...

Страница 5: ...culated Yes Off Auto Yes If desired enter a value less than estimated capacity Yes Yes Yes Off Any Number Yes Yes Automatically calculated Yes Any Number Auto Yes Yes If desired enter a value less tha...

Страница 6: ...he preset regeneration time For Valve Type 1 0T press and hold CLOCK and for about 3 seconds to initiate an exchange of the tank in Service without cycling the regeneration valve After tank switch day...

Страница 7: ...lease Then press NEXT and simultaneously for 3 seconds and release If screen in Step 2CS does not appear in 5 seconds the lock on the valve is activated To unlock press NEXT and CLOCK in sequence then...

Страница 8: ...y Set System Capacity OEM Softener System Setup Step 8S Set to AUTO Set to AUTO OEM Softener System Setup Step 9S Set regeneration time option to IMMEDIATE REGEN Set regeneration time option to IMMEDI...

Страница 9: ...e returned to Service until the error is corrected and reset Retracted Valve A in Service Position MAV piston rod Retracted Extended Valve B in Service Position MAV piston rod Extended Note Clack Twin...

Страница 10: ...SOURCE Allows Auxiliary MAV to switch positions before the start of regeneration and then switch back at the end of regeneration Set OFF Deactivates this output Only use Clack Motorized Alternating V...

Страница 11: ...sed for an accumulative time of 2 minutes a regeneration will occur at the scheduled delayed regeneration time In a twin alternating system once the dP switch is triggered the PC Board will display RE...

Страница 12: ...r until Regenerant Draw DN appears Prior to selecting the upflow regeneration cycle verify that the correct body main piston regenerant piston and stack are being used and that the injector plug s are...

Страница 13: ...s 1 to 480 STEP 1S Step 1S Press NEXT and simultaneously for 3 seconds and release If screen in Step 2S does not appear in 5 seconds the lock on the valve is activated To unlock press NEXT and CLOCK i...

Страница 14: ...ccur immediately when the volume capacity reaches 0 zero or BOTH means regeneration will occur at one of the following the preset time when the volume capacity falls below the reserve or the specified...

Страница 15: ...s Step 10S with the addition of Error Monitor When Error Monitor is selected Relay 2 closes whenever the valve enters the Error Mode and immediately deactivates when Error Mode is exited If set to Off...

Страница 16: ...ediately when volume capacity reaches 0 Time of regeneration will not be allowed to be set because regeneration will always occur when volume capacity reaches 0 Any number IMMEDIATE REGEN OFF Reserve...

Страница 17: ...or 3 seconds and release Step 2F Choose FILTERING using or Press NEXT to go to Step 3F Press REGEN to exit OEM Filter System Setup Step 3F Select the time for the first cycle which in this example is...

Страница 18: ...es of no water usage when the volume capacity reaches 0 zero DELAYED REGEN is the default if Step 4CS is set to VALVE A or VALVE B and BOTH will not be available IMMEDIATE REGEN is the default if Step...

Страница 19: ...een used while in service and then deactivates after a set period of time or after the meter stops registering flow whichever comes first Set REGEN VOLUME Relay activates after a set number of liters...

Страница 20: ...o return to previous step STEP 6I STEP 6I Next Regeneration Time hour Set the hour of day for regeneration using or The default time is 2 00 This display will show not to be viewed if IMMEDIATE is sel...

Страница 21: ...system Contact information will be displayed if it was edited For concerns with phone number or banner text displays contact OEM for instructions The fifth display will show either DP or HOLD if the...

Страница 22: ...the system calls for it usually referred to as manual regeneration There may be a period of heavy water usage because of guests or a heavy laundry day To initiate a manual regeneration at the preset d...

Страница 23: ...icates the time of day should be reset and the non rechargeable battery replaced The system will remember the rest Error Message If the word ERROR and a number are displayed contact the OEM for help T...

Страница 24: ...This display will equal zero if a water meter is not installed Press NEXT to go to Step 4D Press REGEN to return to previous step STEP 4D STEP 4D Reserve History Volume used for last 7 days If the val...

Страница 25: ...ll active MAV drives Use or to review the history of all active MAV outputs TTT measured MAV drive time VVV measured MAV drive voltage CCC total number of drives in or out indicates piston drive into...

Страница 26: ...s display shows the total number of regenerations that have occurred since startup Press NEXT to go to Step 5VH Press REGEN to return to previous step STEP 5VH STEP 5VH Volume total used since start u...

Страница 27: ...each tank until the next regeneration Prior to selecting the upflow regeneration cycle verify that the correct body main piston regenerant piston and stack are being used and that the injector plug s...

Страница 28: ...Page 28 CK and EQ Manual Form No V3435CK 6 16 2014 U S Patents 6 402 944 6 444 127 6 776 901 Translation supported by Pollet Water Group...

Отзывы: