Button appearance and position may be different than actual valve
Cycle times, sequences, and settings in this guide are only examples of how your system may be programmed.
Actual settings are determined by the manufacturer. Please contact them if more information is needed.
Important button sequences to note:
1.
UNLOCK VALVE SETTINGS:
Press buttons in the following order:
–
,
NEXT
,
+
,
CLOCK
. This will allow a user to change
manufacturer’s settings. When finished, lock settings by inputting the same sequence.
2.
CLEAR ERROR ON SCREEN:
Press and hold
NEXT
and
REGEN
for three seconds.
3.
CLEAR SERVICE ALARM:
If service alarm is triggered, press and hold
+
and
–
buttons simultaneously for three
seconds to reset to original set points. This will reset both gallon and year alarms.
4.
REGEN BUTTON:
From a general operation screen, pressing the
REGEN
button schedules a regeneration for that
night. Pressing it again will cancel the regeneration for that night. On most screens besides the general operation
screens, the
REGEN
button works as a “back” button. Pressing it will return to the previous setting screen.
General Operation Screens
Press
NEXT
button to toggle between one of four displays.
Press
REGEN
button to schedule a regeneration for that night.
Return to general display
Displays current time
Unit defaults to this screen after a reset.
Displays a unit’s remaining capacity
This screen will not display if the unit’s gallons of
capacity is set to OFF. “REGEN TODAY” will alternate
with the current screen header if a regen is expected
that night.
Displays days remaining until a regen
This screen will not display if the unit’s day override
is set to off.
Set hours with + or — buttons
AM/PM toggles after 12 AM.
Displays time remaining in current regeneration cycle
“2” flashes for a second backwash if two backwashes are
programmed.
Displays time remaining incurrent cycle
If a chlorine generator is connected and set to ON, the
brine concentration will be checked during draw. Text will
alternate between DRAW TIME & GENERATOR ON.
Set minutes with + or — buttons
AM/PM toggles after 12 AM.
Set current day with + or — buttons
The default setting is WED.
Displays scrolling dealer
name and phone number
To change dealer name and
phone number, see page 3.
Displays current flow rate
“Current Flow Rate” is the amount of water currently
flowing through, and being treated by, the unit. “GPM”
and the flow rate flash while the turbine is rotating.
555 5555555
DEALER NA
If set, a scrolling
dealer name and
phone number
screen will
alternate with the
selected general
operation screen.
CURRENT DAY
SET
WED
TIME
MINUTES
SET
TIME
HOUR
SET
2:00
2:35
AM
AM
MIN
BACKWASH REMAINING
2
3:30
GENERATOR ON
53:45
Unlock and Lock Controller
The following screens will flash when the correct button sequence is
inputted to unlock valve settings.
Indicates that the valve controller is unlocked
Unlocks access to advanced programming features
within the controller.
Indicates that the valve controller is locked
It is strongly advised to lock the controller following any
changes. This helps to prevent any accidental access to
advanced programming settings.
PROGRAM
UNLOCK
PROGRAM
LOCK
DAYS TO A REGEN
GPM
3
8
CAPACITY REMAINING
GPM
GAL
1600
8
FLOW RATE
GPM
8.0
TIME OF DAY
MON
GPM
2:40
8
PM
Set Time Screens
Typical Regeneration Screens
Accessed by pressing the
CLOCK
button.
Only visible when unit is in regeneration
The symbol on the following pages indicates
that the screens below it will not display unless the
controller is unlocked.