Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E
- 7 -
Online UPS-Type
400 kVA
500 kVA
600 kVA
800 kVA
Output
Output apparent power (cos
φ = 0,9)
400 kVA
500 kVA
600 kVA
800 kVA
Output active power (cos
φ = 1)
360 kW
450 kW
540 kW
720 kW
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
-
Tolerance dynamic load (20 % → 100 % → 20 %)
- Correction time after load step
3 x 380/220 V
3 x 400/230 V
3 x 415/240 V
±1 %
±2 %
±5 %
< 20 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
50/60 Hz
±0,001 Hz
±2 Hz
Rated output current (cos
φ = 0,9)
580 A
724 A
870 A
1060 A
Rated output current (cos
φ = 1,0)
522 A
651 A
783 A
954 A
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
< 1 %
< 5 %
Input
Input voltage
3 x 400/230 V +15 % -20 %
Input frequency
50/60 Hz ±5 Hz
Input current (at 100 % load, without battery charging)
550 A
687 A
824 A
1099 A
Input current (at 100 % load, max. battery current)
610 A
767 A
904 A
1220A
Input power factor (at 100 % load)
> 0,99
Input current THD (at 100 % load)
< 3 %
Battery
Number of battery cells
300
Compensation charging voltage
680 V (2,27 V/Z)
Cut-off voltage
496 V (1,65 V/Z)
Max. battery charging current (at 100 % load)
60 A
80 A
120 A
Max. battery charging current with activated DCM
(
D
ynamic
c
harging
m
ode, only at partial load)
100 A
200 A
Battery charging characteristic
IU (DIN 41773)
Overload capability/Output short circuit characteristic
Overload capability inverter
>100 % to 125 % for 10 min
> 125 % to 150 % for 1 min
= 150 % for 10 s
Overload capability static bypass
150 % continuously
1000 % for 1 cycle
Short circuit characteristic (Bypass is available)
Immediate transfer to the bypass
Short circuit characteristic (Bypass is not available)
1. Current limitation to 150 % for 150 ms
2. Current limitation to 125 % for another 5 s
695 A
579 A
870 A
725 A
1044 A
870 A
1390 A
1158 A
Design/Conformity
Dimensions (W x H x D)
1990 x 1920 x 990 mm
2440 x 2020 x 990 mm
3640 x 1920 x 990 mm
Weight (without battery)
1820 kg
2220 kg
2400 kg
3600 kg
Paint
RAL 5026 / RAL 9006
Noise level
< 60 dB
EMV-class according to IEC EN 62040-2
C3
Class of protection according to IEC EN 62040-3
VFI SS 111
International protection
IP 20
Other data
Efficiency normal mode (at 100 % load)
> 94,5 %
Efficiency battery mode (at 100 % load)
> 96 %
Efficiency eco-mode (offline-mode)
> 98 %
Max. crest factor without power reduction
3 : 1
Heat dissipation
(at 100 % load and rated input voltage)
22,0 kW
27,5 kW
33,0 kW
43,3 kW
Requirements to the installation position
Max. installation altitude without power reduction
< 1000 m
Power reduction for installation altitude according to
IEC EN 62040-3
1 % every 100 m above 1000 m up to 5000 m
Required air cooling volume
3500 m³/h
4000 m³/h
4500 m³/h
7000 m³/h
UPS operating ambient temperature
0 to +40 °C
UPS storage temperature
-10 to +70 °C
Battery ambient temperature
(recommended battery ambient temperature, see also
battery operating instruction)
0 to +25 °C
+20 °C
Battery storage temperature
0 to +25 °C
Relative humidity (non condensing)
< 95 %
Содержание JOVYSTAR HP 200 kVA
Страница 1: ...Operating manual W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E...
Страница 17: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 17 4 3 1 Dimensions W rtsil JOVYSTAR HP E 200 300 kVA...
Страница 18: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 18...
Страница 19: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 19 4 3 2 Dimensions W rtsil JOVYSTAR HP E 400 kVA...
Страница 20: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 20...
Страница 21: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 21 4 3 3 Dimensions W rtsil JOVYSTAR HP E 500 600 kVA...
Страница 22: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 22...
Страница 23: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 23 4 3 4 Dimensions W rtsil JOVYSTAR HP E 800 kVA...
Страница 24: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 24...
Страница 25: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 25...
Страница 28: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 28 Terminal board 400 kVA...
Страница 29: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 29 Terminal board 500 800 kVA...
Страница 30: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 30 4 4 2 Internal Connections between both switch cabinets...