Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E
- 57 -
Alarm
A48 FAILED RECEPTION OF EEPROM PARAMETERS
Description
Internal error.
Possible
causes
Microcontroller communication problems.
Solutions
1. Contact our Technical Support Service.
Alarm
A49 TEST MODE DISCREPANCY
Description
Internal error.
Possible
causes
Microcontroller communication problems.
Solutions
1. Contact our Technical Support Service.
Alarm
A50 STATIC SWITCH BLOCKED
Description
The static switch is blocked. The load is no longer supplied.
Possible
causes
Loads failure.
Possible UPS fault.
Solutions
1. Check the loads for possible failures.
2. Reset the system.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A51 BATTERY TEMPERATURE OUT OF TOLERANCE
Description
The battery temperature is out of tolerance. This alarm is only active when the temperature probe is installed and enabled on
the battery.
Possible
causes
Anomalous temperature in the battery cabinet.
Possible failure on the measuring circuit.
Solutions
1. Check the temperature on the batteries and remove the cause of the alarm, if any.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A52 DC COMP ERROR
Description
Internal error.
Possible
causes
Microcontroller communication problems.
Solutions
1. Contact our Technical Support Service.
Alarm
A53 FIRMWARE CONFIGURATION ERROR
Description
The controller has detected an incompatibility in the control software.
Possible
causes
The software update was not performed properly.
Solutions
1. Contact our Technical Support Service.
Alarm
A54 PARALLEL CAN COMMUNICATION ERROR
Description
Internal error.
Possible
causes
Microcontroller communication problems.
Solutions
1. Contact our Technical Support Service.
Alarm
A63 STARTING SEQUENCE BLOCKED
Description
During the UPS start-up a failure prevented the proper execution of the sequence.
Possible
causes
Control devices in wrong position or operated improperly.
Possible internal fault.
Solutions
1.
Make sure the position of the control devices (isolators, selectors) is as specified in the procedures (see “Installation and start-up”
section).
2. If the alarm persists, contact our Technical Support Service.
8.1
Measures in case of problems
WARNING:
Please contact our Service-Department after a failure.
Содержание JOVYSTAR HP 200 kVA
Страница 1: ...Operating manual W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E...
Страница 17: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 17 4 3 1 Dimensions W rtsil JOVYSTAR HP E 200 300 kVA...
Страница 18: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 18...
Страница 19: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 19 4 3 2 Dimensions W rtsil JOVYSTAR HP E 400 kVA...
Страница 20: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 20...
Страница 21: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 21 4 3 3 Dimensions W rtsil JOVYSTAR HP E 500 600 kVA...
Страница 22: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 22...
Страница 23: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 23 4 3 4 Dimensions W rtsil JOVYSTAR HP E 800 kVA...
Страница 24: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 24...
Страница 25: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 25...
Страница 28: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 28 Terminal board 400 kVA...
Страница 29: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 29 Terminal board 500 800 kVA...
Страница 30: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 30 4 4 2 Internal Connections between both switch cabinets...