![WÄRTSILÄ JOVYSTAR HP 200 kVA Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/wartsila/jovystar-hp-200-kva/jovystar-hp-200-kva_operating-manual_3468610016.webp)
Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E
- 16 -
4.3
Setting up
The UPS must be installed in a clean and dry room, preferably not dusty. The user must ensure a proper air conditioning
for cooling the equipment. If the UPS contains the batteries internally the air exchange with the external ambient must
comply with EN 62040, annex N.
Pay attention, that through the weight of the UPS and the batteries the maximum floor loading will not exeeded. You find
informations to the weights and the measurements in the technical data. In addition the site must fulfil the following re-
quests:
-
The UPS may be installed only in dry rooms.
-
None caustic or acid steam may escape.
-
The device supply air temperature may be maximally 40°C.
-
Whem batteries are supplied to this UPS installation, the air exchange for these batteries with the external sur-
roundings must according to EN 62040 appendix N.
-
The vent holes at the device must not be covered by construction measures or other factors.
-
The device is to be protected against direct solar radiation and action of other heat springs.
-
The wall- and ceiling-distances as well as the recommended air flow volume (see also technical data) are com-
plying for an optimum cooling of the UPS. An overheating of the system is thus avoided.
Содержание JOVYSTAR HP 200 kVA
Страница 1: ...Operating manual W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E...
Страница 17: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 17 4 3 1 Dimensions W rtsil JOVYSTAR HP E 200 300 kVA...
Страница 18: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 18...
Страница 19: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 19 4 3 2 Dimensions W rtsil JOVYSTAR HP E 400 kVA...
Страница 20: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 20...
Страница 21: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 21 4 3 3 Dimensions W rtsil JOVYSTAR HP E 500 600 kVA...
Страница 22: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 22...
Страница 23: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 23 4 3 4 Dimensions W rtsil JOVYSTAR HP E 800 kVA...
Страница 24: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 24...
Страница 25: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 25...
Страница 28: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 28 Terminal board 400 kVA...
Страница 29: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 29 Terminal board 500 800 kVA...
Страница 30: ...W rtsil JOVYSTAR HP 200 800kVA BAX 4640 E 30 4 4 2 Internal Connections between both switch cabinets...