21
18. Tracing faults
Red LED
Green LED
Glo
w
in
g
per
ma
ne
ntl
y
Fl
as
hi
ng
q
uic
kly
Fl
as
hi
ng
slowly
Off
Glo
w
in
g
per
ma
ne
ntl
y
Fl
as
hi
ng
q
uic
kly
Fl
as
hi
ng
slowly
Off
Status
Probable reasons
Possible remedy
x
x Actuator does not respond, both
LEDs are off
1) No supply voltage applied
2) The applied voltage does
not match the actuator
voltage on the tag plate
1) Check mains supply
2) Apply correct supply
voltage
x
x
Actuator does not drive the full
stroke
1) Actuator not correctly
commissioned
2) Too small stroke
programmed (in mode “one
position‐dependent cut‐
off”)
1) Repeat commissioning
2) Check valve stroke
parameters ‐> see
instructions AMS‐PSCS
x
x
Actuator does not close the valve
properly
1) Actuator not correctly
commissioned
2) Actuator closing force/
torque too low
1) Repeat commissioning
2) Check actuator selection
x
x
Actuator is in normal operating
condition, but does not respond to
set‐value changes
1) Fixed digital set‐value is
activated
2) Actuator is configured to
work with process
controller
1) Check set‐value
parameters ‐> see
instrucions AMS‐PSCS
2) Connect process sensor
x
x
Actuator position does not
correspond to set‐value input
A non‐linear valve curve has
been parameterised
Verify parameterised
characteristic ‐> see
instructions AMS‐PSCS
Operating conditions
Probable reasons
Possible remedy
x
x
Normal operating condition
x
x
Actuator in commissioning mode
Commissioning mode will be
left automatically after
completion
x
x
Actuator not commissioned
Depending on the type of
cut‐offs, the actuator has to
be commissioned either
automatically or manually
Faults within the actuator’s
environment
Probable reasons
Possible remedy
x
x
Too high torque has been
encountered within the valve stroke
1) Actuator not correctly
commissioned to the valve
2) Mechanical block within
the stroke path
3) Improper selection of the
actuator
1) Repeat commissioning
2) Check valve and actuator
for unobstructed running
3) Check actuator selection
x
x
1) No proper process feedback (only
in combination with PSIC)
2+3) Maximum control range
exceeds (only in combination with
PSIC)
1) Process feedback wrongly
or not at all connected
2) Process feedback outside
od adjusted range
3) No process sensor signal
available
1) Apply the correct process
feedback signal and check
polarity
2) Ensure the correct process
feedback range
3) Check the process sensor
and its supply voltage
Содержание ARIA Series
Страница 7: ...Preliminary 7 ILEA A B_IOM_NoRev_1118 DEFAULT PARAMETERS SOFTWARE SET UP...
Страница 9: ...Preliminary 9 ILEA A B_IOM_NoRev_1118 ACTUATOR REMOVAL REPLACEMENT INSTRUCTIONS...
Страница 11: ...Preliminary 11 ILEA A B_IOM_NoRev_1118...
Страница 14: ...Preliminary 14 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com...
Страница 15: ...Preliminary 15 ILEA A B_IOM_NoRev_1118...