USAGE AS PER SPECIFICATION
• ARIA Series actuators are exclusively designed to be used as
electric valve actuators for rising stem globe control valves.
They are meant to be mounted on Warren Controls, control
valves in order to run their motors.
• Any other use is considered to be non-compliant and the
manufacturer cannot be held liable for any damage resulting
from it.
• The actuators can only be used within the limits laid out in the
data sheets, catalogues and other documents. Otherwise, the
manufacturer cannot be held liable for any resulting damage.
• Usage as per specification includes the observance of the
operating, service and maintenance conditions laid down by
the manufacturer.
• Read this document in its entirety as special precautions
need to be taken before mounting and adjusting the actuator
as well as servicing!
• The actuators may only be used, serviced and repaired by
personnel that is familiar with them and informed about
potential hazards. The specific regulations for the prevention
of accidents have to be observed.
• Damages caused by unauthorized modifications carried
out on the actuators are excluded from the manufacturer’s
liability.
• Supply voltage may only be switched on after the proper
closure of the main cover or terminal box.
ILEA SERIES BASIC SPECIFICATIONS
Spring-Fail
ARIA
Stroke Speed
12 Secs/In., (2 mm/sec.), Fixed.
Spring-Fail Speed: 2.3 mm/sec.
What happens under the condition of Loss
of Power, under voltage or over voltage.
Actuator engages Spring Fail, to Open or Close, Depending on model.
What happens under the condition of
Loss of Control Signal.
Actuator engages Spring Fail, to Open or Close, Depending on model. With control by
binary inputs, actuator stops in position when event occurs.
MAX Thrust: 455 Lbf (2kN)
MAX Stroke: 1.38 In. (35mm)
Manual Override (electric): via 2 push buttons when powered
Power Supply: 24 VAC/DC, optionally wide range PS (100-240 VAC)
Motor protection: Electronic motor current monitoring with safety cut-off
Duty cycle as per IEC 60034-1,8: S2 30 min/ S4 1200c/h-50% ED
Permitted ambient temperature: -4ºF to 140ºF (-20ºC to +60ºC)
Internal fault monitoring: Thrust, Control Signal, Temperature, Power Supply
Binary control: 24-230- VAC for ON/OFF service
Control Signal and Feedback: 0-20 mA, 4-20 mA, 0-10 V, 2-10 V selectable, plus split range
Mounting Position: Any position, except cover pointing downwards
Conduit entries: 2 pcs. M 20 x 1.5 /1 pc. M 16 x15
Enclosure Rating. to EN 60529: IP67
Fuse - HV Power Supply: 2 AMP, 5 x 20 mm, 250 VAC, Slow Blow
POWER CONSUMPTION
25 WATTS, MAX CURRENT
1.8 A at 24 VAC / DC
0.36 A at 115 VAC
0.18 A at 230 VAC
OPERATING CONDITIONS AND INSTALLATION POSITION
• Standard actuators may be operated at ambient temperatures according to the
ARIA Series basic specifications.
• Operating modes correspond to IEC 60034-1, 8: S2 for short cycle and S4 for
modulating operation.
• For protection against moisture and dust, the enclosure rating is IP65 according
to EN 60529.
• When installing the actuators, leave enough space to allow cover removal.
• The actuator can be installed vertically or horizontally or any position in between.
The actuator must not be installed with the cover pointing downwards.
Outdoor usage:
When using the actuators in environments
with high temperature fluctuations or high humidity, we
recommend using the optional heating resistor. IP67
Installation
positions
Содержание ARIA Series
Страница 7: ...Preliminary 7 ILEA A B_IOM_NoRev_1118 DEFAULT PARAMETERS SOFTWARE SET UP...
Страница 9: ...Preliminary 9 ILEA A B_IOM_NoRev_1118 ACTUATOR REMOVAL REPLACEMENT INSTRUCTIONS...
Страница 11: ...Preliminary 11 ILEA A B_IOM_NoRev_1118...
Страница 14: ...Preliminary 14 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com...
Страница 15: ...Preliminary 15 ILEA A B_IOM_NoRev_1118...