The connection of three phase input cable
1)
The installation have to accord with related standard, and operate by professional
persons;
2)
Shut off the breaker of power, the connection operation only be allowed after
turning off;
3)
This machine use 3 phase 380V, 50Hz, user have to prepare relevant distribution box,
air breaker and power cables. The power condition as the below sheet:
Model
The sectional area of
input coppercable (mm
2
)
The sectional area of
ground cable (mm
2
)
Fuse (A)
Contact capacity
(A)
AIRCUT
-
101I
≥6
≥6
60
63
AIRCUT
-
160IW
≥10
≥10
80
80
AIRCUT
-
200IW
≥16
≥16
125
125
4)
The connection of power lead
Use eligible cables and sockets to connect it, and must be operated by a
qualified electrician.
5)
Connection of groundcable
Connect the green-yellow wire of power source cable to ground ( Model
AIRCUT
-101I please connect it to ground on marking
of the machine
body) , the sectional area must match the requirements in above form, to ground
firmly. Ground connecting method should follow state standard.