background image

South Bend, Indiana USA 

 |

  networketi.com

PT-SINGLE

 INSTALLATION MANUAL  |  PART NO. 

25166

 REV 

D

6

PANEL LOCKOUT

To prevent unauthorized changes of control settings, the 

second DIP switch can be set to the on position to Lock 

the settings. With Lock enabled, the control panel will 

allow viewing but not changing any of the settings; only 

the °C or °F option can be changed. See Figure 6.

Note:

 The GPT reads the Lock DIP switch position when

the Settings screen is entered. If the switch is changed,

you need to re-enter the Settings screen.

EXTERNAL ALARM

Alarm Connections

An alarm or power–off condition can be communicated 

by either opening or closing a relay contact. It is important

 

to make the proper alarm relay connections to achieve 

the desired result. The middle terminal labeled COM 

(Common) is used in both wiring configurations. Connect 

one alarm relay lead to the COM terminal.

If the system needs a contact to close to signal an alarm or 

power–off condition, connect the other alarm relay lead 

to the NC (Normally Closed) terminal. See Figure 7.

If the system needs a contact to open to signal an alarm 

or power–off condition, then connect the other alarm 

relay lead to the NO (Normally Open) terminal.

If the unit has power, and there are no alarm conditions 

then the NO and COM terminals will be connected. If the 

unit loses power or an alarm condition occurs then the 

NC and COM terminals will be connected.

Note:

 The “Normally” condition of the relay is the alarm 

condition for the unit.

OPERATION

The 

PT-SINGLE

  can  maintain  temperatures  from  a 

setpoint 

ranging from −99.9 °F to 999.9 °F (−73.3 °C to 

537.7  °C).

 

The  usable  temperature  range  is  sensor 

dependent.  The 

heater  will  energize  when  the 

temperature  drops  below  the  designated  setpoint. The 

heater will de-energize when 

the  temperature  meets  the 

designated High Temperature.

The 

PT-SINGLE

  features  ETI’s  patented  self–testing 

GFEP,  which  switches  the  system  off  when  it  detects 

excessive ground current leakage. The GFEP eliminates 

the extra expenses associated with having to provide an 

external GFEP.

Alarms

Critical Alarms are Latching alarms and include Ground 

Fault, High Current, Stuck Relay, Internal Circuit, and 

FIGURE 6. Panel lockout DIP switch configuration

Wiring to normally closed 

alarm contact

FIGURE 7. External alarm connection

Setting for

Panel Lockout ON

(default is OFF)

Содержание TRACON PT-SINGLE

Страница 1: ...l Odor or Smoke In the event of smoke or a burning or abnormal odor immediately interruptpowertotheunitbyturningoff thecircuitbreakerprotecting the unit Electrical Shock Fire Hazard Any installation i...

Страница 2: ...nection The internal load contactor is rated to South Bend Indiana USA networketi com switch up to 30 A resistive The Integral GFEP provides safety in compliance with national and local electrical cod...

Страница 3: ...e only Listed Type 4X IP66 liquid tight conduit hubs or cable glands Connect the hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cab...

Страница 4: ...PST contacts rated for heater loads up to 30 A ac and 277 V ac These two contacts are used to control both legs of the input power Line and Neutral Manual Load Test To manually energize the load selec...

Страница 5: ...to 230 F 40 C to 110 C See Figure 5 for proper wiring when using a thermistor sensor RTD The unit can use an RTD sensor for applications requiring a wider temperature range The PT SINGLE can operate...

Страница 6: ...contact to open to signal an alarm or power off condition then connect the other alarm relay lead to the NO Normally Open terminal If the unit has power and there are no alarm conditions then the NO...

Страница 7: ...en the heater is energized LOW TEMP indicator This blue LED indicates when sensors detect temperature has fallen below the Low Temp Alarm threshold ALARM indicator This red LED indicates when there is...

Страница 8: ...Load Current alarm you must view the Load Current Display screen Note If the heater relay is off the ground fault number is NOT shown Temperature Display screen Indicates the current temperature in Fa...

Страница 9: ...eens that display multiple fields there are two columns The left column displays the name of the parameter and the right column displays the current value Initially one of the fields in the left colum...

Страница 10: ...South Bend Indiana USA networketi com PT SINGLE INSTALLATION MANUAL PART NO 25166 REV D 10 FIGURE 10 Setting screen sequence...

Страница 11: ...High temperature alarm delay 0 s to 3000 s Default 300 s Low current alarm threshold 0 0 A to 10 0 A Default 0 1 A Enabled Low current alarm delay 0 s to 300 s Default 5 s Enabled High current alarm t...

Страница 12: ...to mark the Return Merchandise Authorization clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about...

Отзывы: