FLUE DETAILS DIMENSIONS

 

Minimum Flue Height

 

  

Flue Height

 

3600

 

Measured From Top of Adaptor

 

B + F + 3600

 

Flue Details

 

No:

 

TF 800

 

TF 1000

 

TF 1200

 

Cowl

 

1

 

300

 

300

 

350

 

Top Spider

 

1

 

300

 

300

 

350

 

Cone

 

1

 

300

 

300

 

350

 

Flue Diameter

 

3

 

300

 

300

 

350

 

Liner Diameter

 

3

 

400

 

400

 

450

 

Spacer

 

3

 

300/400

 

300/400

 

350/450

 

NOTE: 

Ensure that a Standard Tested Warmington Flue system is used on the Warmington fires.

 

FLUE SYSTEM INSTALLATION GUIDE 

 

1.

 

Install the first length of flue pipe with the crimped end down, inside the Adaptor collar, ensure 
that the flue pipe is sealed into the collar with exhaust sealant. Rivet the flue in 3 places around 
the Adaptor collar. Place a spacer around the flue pipe approximitaly150mm above the adaptor 
collar. Secure in position by tightening the screw and nut.

 

2.

 

Install the second length of flue pipe with the crimped end down and fit by riveting in at least 3 
places around the flue pipe joint. Ensure that the flue is sealed into position with sealant.

 

3.

 

Install the first section of flue pipe liner with the Crimped end up, over the flue pipe and over the 
spacer that is fixed to the flue pipe. This spacer will keep the liner concentric about the flue pipe.

 

4.

 

Position flue spacer at the flue pipe joint for every length of “Flue pipe” and “Liner”.

 

5.

 

Repeat the Steps from 1 – 4 to the installed required height of the flue system. The flue system is 
to comply with ASNZS 2918:2001 4.9.1 

 

 

NOTE:

 The last length of flue pipe needs to extend past the liner so that when the “top spider” 

 

and 

the “Flashing cone” are fitted, that the “flashing cone” and the “flue pipe” are 

flush,

 or that the “flue pipe” 

is 

5mm lower

 that the “Flashing cone”.

 

5.

 

Fit the “Top Spider” into position, ensure that the legs of the spider are fitted inside the liner and 
that the spider is positioned hard down onto the liner and tighten with the screw and nut. 

 

6.

 

Place the “Flashing cone” over the “flue pipe” and press hard down onto the “Top Spider”. (Note 
that the “Flue pipe” and the “Flashing Cone” are either flush or the “Flue pipe” is 5mm Lower than 
the “Flashing cone”.) Ensure that the “Flashing cone” is clear for the venting from the “Liner” and 
the “flue pipe”.

 

7.

 

Fit the “Cowl” to the top of the flue pipe. The “Cowl”, “Flashing cone”, and the “Flue pipe” can be 
secured to each other with the uses of a stainless steel self tapping screw. This will allow the 
“Cowl” to be removed for cleaning.

 

Flue system may require Bird Proofing due to the installation and locations, discuss this with your install-
er for the best advice.

 

If the Flue system is installed into a “Chimney Chase”, allow for air vent as close to the top of the chase 
as practical, or allow venting through the “Chimney Chase Flashing”. A “Venting Flashing cone” and a 
25mm gap around the Liner with a “Venting Flashing Cone

-

Spider” can be used. 

 

 

 

a “the flue pipe shall extend not less than 4.6m above the top of the floor protector.”

 

 

b “ the minimum height 

of the flue system within 3 m distance from the highest point of the roof shall be 600mm 

above that point.”

 

 

c “the minimum height of the flue system further than 3 m from the highest point of the roof shall be 1000mm 
above the roof penetration.”

 

 

d “no part

 of any building lies in or above a circular area described by a horizontal radius of 3 m about the flue 

system exit.”

 

SINGLE 3.6m FLUE KIT DETAILS

 

Note: FLUE SYSTEMS Casing….

 

Flue  system  may  require  to  be  Doubled  lined  to  comply. 
Ref ASNZS:2918:2001 4.3 Flue pipe casing

 

This is a general installation guide only – Contact a “NZHHA Installer” for Installation Advice or go 
to www.homeheat.co.nz then select Members & follow Instructions , to find a Certified NZHHA SFAIT 

Содержание TFG 800

Страница 1: ...ence Ensure that you have the correct and current installation details for the Warmington Fire Installation The Warmington unit is to be installed by a certified Warmington installer or an approved NZ...

Страница 2: ...c Perf Extension 2 Back Air Brick 1 NOT Supplied sold separately No Warmington Fluekit 1 Fire Bricks H40 75X115X230mm Other Sizes Available Varied Fire Brick Refractory Mortar 1 Autoclaved Aerated Con...

Страница 3: ...atural convection exits through the vents at the top of the cavity or through the liner and out of a venting cone in the case of venting through the flashing 1 2 3 3 4 POINTS TO CONSIDER PRIOR TO INST...

Страница 4: ...supply valve beside your meter Call your gas supplier gasfitter or the fire service for further advice GENERAL REQUIREMENTS FLUED GAS APPLIANCES All gas fires requiring Warmington Flue Systems shall b...

Страница 5: ...G ELECTRONIC GAS FIRE AS SHOWN FROM THE FRONT OF THE BURNER This control panel is located on the bottom left hand side of your Warmington decorative gas fire Press and release the power button This wi...

Страница 6: ...ce requirements Construct framing or block surround according to relevant minimum dimensions as referenced on pages 6 to 9 After framing surround is complete construct plinth to required height see pa...

Страница 7: ...DETAILS HEAT CELL CLEARANCE Description TFG 800 TFG 1000 TFG 1200 To centre of flue J 539 538 589 Flue diameter K 300 300 350 Liner diameter L 400 400 450 Heat cell clearance width M 1290 1490 1690 H...

Страница 8: ...00 600 750 Block clearance width R 1610 1610 2010 Block clearance depth S 1000 1000 1200 Block enclosure height U 2390 2390 2390 To centre of flue V 639 638 689 Chimney chase clearance X 500 500 550 N...

Страница 9: ...h RR 1590 1990 1990 Solid poured top depth SS 1190 1190 1190 Block enclosure height TT 2390 2390 2390 To centre of flue UU 554 553 604 Chimney chase clearance X 500 500 550 Note Centreline of flue is...

Страница 10: ...to firebox using supplied M8 bolts nuts and washers Ensure that exhaust sealant is used between fire and adaptor Construct autoclaved aerated concrete AAC enclosure around traditional firebox Insert...

Страница 11: ...ard of the front face of the fireback or where the gas burner is expected to be placed Additionally lay up the first layer s of the fireback leaving one brick s worth of a gap in the centre of the bas...

Страница 12: ...anels 2400x600x75 Power Panels are required for basic heat cell construction as shown in detail Firebox with Hebel Surround Visit www warmington co nz site for AAC instructions PDF download 2 3 2 TFG...

Страница 13: ...Pressure High kPa 1 1 1 Burner Pressure Low kPa 0 3 0 3 0 3 MJ h 35 61 27 Flame Effect Output Only Effect Effect Effect Supply Pipe Size minimum diameter 3 8 1 2 3 8 Lab Test No GL 923 WAR 0115 0121...

Страница 14: ...effect Fit burner grate by sliding R L side metal pins on grate into holes located on burner side plates as shown 2 Top Row Slide R LH grate pins into holes located on the burner side 1 Bottom Row Tot...

Страница 15: ...to the hi kPa value in the table for maximum output test point inlet Modulator Harness Connections 1 2 BSPT gas outlet SIT 840 Control Valve test point outlet 1 2 BSPT gas inlet adjustment screw Afte...

Страница 16: ...5 September 2019 All dimensions are in mm Copyright 16 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification...

Страница 17: ...between the hi and the low pressures test point inlet HI LOW Harness Connections test point outlet 1 2 BSPT Gas outlet SIT 843 Control Valve Nut A High setting adjustment screw Screw B Low setting ad...

Страница 18: ...5 September 2019 All dimensions are in mm Copyright 18 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification...

Страница 19: ...asfitter Light appliance adjust to high flame setting and check pressure adjust to low flame and check pressure If adjustments are necessary remove the cap The pressure adjustment screw and nut are on...

Страница 20: ...tisfied that the appliance is working correctly fit the front panel assembly back to the gas burner NOTE Ensure you peel the Protective Plastic Coating from any stainless steel components if fitted Al...

Страница 21: ...5 September 2019 All dimensions are in mm Copyright 21 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification...

Страница 22: ...e base screw and check for leaks Correct operation of 3 Flame Pilot 3 Flame Pilot in 3 7 COMMISIONING AND TESTING Read all the instructions before commissioning Install coals and logs and burner befor...

Страница 23: ...graph for a selected model of traditional fire is an acceptable hearth extension A hearth extension BELOW the curved minimum requirement line is NOT acceptable 4 1 COMBUSTIBLE MANTLE CLEARANCES REF B...

Страница 24: ...ue pipe is 5mm lower that the Flashing cone 5 Fit the Top Spider into position ensure that the legs of the spider are fitted inside the liner and that the spider is positioned hard down onto the liner...

Страница 25: ...LINED FLUE SYSTEM FLUE PENETRATION VENTED THROUGH TOP FLASHING Note Flue system casing Flue system may require to be Doubled lined to comply Ref ASNZS 2918 2001 4 3 Flue pipe casing Notes External re...

Страница 26: ...tion CHIMNEY CHASE FLASHING AND AIR VENTILATION OP TIONS SETTING ADD COWL AND FLASHING CONE HEIGHT Note Flashing Spigot height is determined by the Insulation that is fitted under the Flashing See Det...

Страница 27: ...ations without prior notification FLUE HEIGHT MINIMUM DETAILS FRAME OUT AND TRIM OUT DETAILS FOR CHIMNEY CHASE Option X Singled Lined Flue System Option Y Double Lined Flue System The flue exits are t...

Страница 28: ...E APPLIANCE SHALL BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH THE MARKING TESTED TO AS NZS 4013 ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING AUTHORITY IS CONSI...

Отзывы: