20

 

ON

-

OFF

-

HIGH

-

LOW ELECTRONIC CONTROL VALVE

 

Note: Any alterations to pressure is to be carried out by a Certified Gas Fitter.

 

 

• 

Light appliance and check the pressure to the high and low kPa values in the gas specification table.

 

• 

If adjustments are necessary, remove the dust cap on the control value. The pressure adjustment screw is on the front side of the 
gas control valve and is factory set.

 

 

WARNING: 

Ensure that the dust cap is replaced after adjustment.

 

 

Pressure Setting

:

 

• 

Turn the burner on with the switch and wait for full ignition.

 

• 

If adjustments are necessary, remove the cap . The Pressure Adjustment Screw and Nut are on the Front Side of the Gas Control 
Valve (shown in diagram 

below

) and are 

Factory 

set.

 

• 

High Pressure Setting

: Set the Burner to High with the switch. Screw in 

Nut A 

to Increase the Outlet Pressure then screw Nut A 

 

out to Decrease the Pressure to the desired settings . Use 10mm spanner.

 

• 

 

Low Pressure Setting: 

Set the Burner to Low with the switch 

-

 See Wiring Diagram) and, keep Nut A stationary . Use a screwdriv

-

 

er to screw in 

Screw B 

to Increase the Pressure and Screw it Out to Decrease the Pressure . Carefully replace the Modulator Plas

-

 

tic Cap.

 

• 

Set the pressure to the hi kPa value in the table for maximum output. The burner will operate any pressure between the hi and the 
low pressures.

 

test point inlet

 

HI / LOW Harness Connections

 

test point outlet

 

1/2” 

BSPT Gas outlet

 

SIT 843 Control Valve

 

Nut A

 

High setting adjustment screw

 

Screw B

 

Low setting adjustment screw

 

• 

After checking the pressure, turn the unit off, remove manometer from the test point and tighten the test point screw.  Ensure to 
check for gas leaks.

 

• 

Ensure power is off & reconnect modulator harness connection in the main harness.

 

• 

Turn the appliance on and off a few times to check ignition.

 

• 

When satisfied that the appliance is working correctly, fit the front panel assembly back to the gas burner.

 

• 

Note: Ensure you peel the protective plastic coating from any stainless steel components if fitted.

 

• 

All burner Aerations are factory preset and cannot be adjusted.

 

• 

If you are unable to get the unit to operate correctly, refer to troubleshooting before contacting your local service contact.

 

• 

It may take approximately 2 hours of operation for the coals/logs or river rocks to achieve their full flame pattern and glow.

 

• 

During the initial burn period, some smoke and smell may be experienced. Because of this, run the appliance on the high position 
in a well ventilated room until fumes dissipate.

 

Содержание SG 700

Страница 1: ...allation The Warmington unit is to be installed by a certified Warmington installer or an approved NZHHA installation technician See www homeheat co nz members for a certified NZHHA SFAIT Installer in...

Страница 2: ...ity to Vent the Warm Air This Warm Air helps keep the Fire and Flue System form getting to Cold If the Flue and Fire get to Cold the System may soot often and require cleaning Each Fire has different...

Страница 3: ...855 855 855 1205 Cabinet Depth C 525 525 525 525 564 Fascia Width D 865 940 1065 1260 1420 Fascia Height E 680 680 680 680 677 Centre of Flue F 315 315 285 285 336 Flue G 200 200 250 250 300 Flue Oute...

Страница 4: ...r Size mm 2 X 1 1mm 2 X 1 2mm 2 X 1 3mm 2 X 1 4mm 4 X 1 1mm Burner Pressure High kPa 2 5 2 5 2 5 2 5 2 5 Burner Pressure Low kPa 0 75 0 75 0 75 0 75 0 75 MJ h 29 38 42 50 60 Flame Effect Output Only E...

Страница 5: ...1700 1850 Hearth Projection Q 300 300 300 300 300 To Wall Side R 100 100 100 100 100 To Wall Behind S 100 100 100 100 100 To Flue Centre T 340 340 340 340 330 Hearth Depth Corner Y 1550 1590 1650 1750...

Страница 6: ...e place Caitec weir vent system as close to fireplace as possible CAITEC TECHONOLGY ROOM AIR REPLACEMENT Caitec draws air from an external air source to ensure that combustion air that the open fire u...

Страница 7: ...t the Top Spider into position ensure that the legs of the spider are fitted inside the liner and that the spider is positioned hard down onto the liner and tighten with the screw and nut 3 Place the...

Страница 8: ...041 20th July 2004 FLUE PENETRATION vented through alcove double lined flue system FLUE PENETRATION Vented through Top Flashing Note External requirements Refer to relevant standards Install flue syst...

Страница 9: ...CHASE FLASHING AND AIR VENTILATION OPTIONS VENTING THROUGH CHIMNEY CHASE No Insulation under flashing VENTING THROUGH FLASHING Insulation under flashing Note Flashing spigot height is determined by t...

Страница 10: ...ange product specifications without prior notification All Dimension are in mm Copyright 10 FLUE HEIGHT MINIMUM DETAILS FRAME OUT AND TRIM OUT DETAILS FOR CHIMNEY CHASE The flue exit is to comply to r...

Страница 11: ...the right to change product specifications without prior notification All Dimension are in mm Copyright 11 Note For Combustible Floors Minimum Hearth of 300mm A must be maintained at any given height...

Страница 12: ...ified on the Data Plate is correct for the available supply LPG or NG A Copper Gas supply capable of supplying the correct MJ h should be brought into the rear of the installation cavity through the h...

Страница 13: ...Logs and twigs may be scattered to achieve best visual effect Fit Burner grate by sliding R L side metal pins on grate into holes located on burner side plates as shown below 2 Top Row Slide R LH Grat...

Страница 14: ...o light all the way across Once the flame is established adjust to the desired setting and close the cover To shut down Open the cover by pulling it outwards Turn the control ignition switch to PILOT...

Страница 15: ...sired pressure see spec s Extinguish Appliance remove test equipment and secure test nipple Check valve burner for correct operation check fire for gas leaks Note When the base screw is removed gas wi...

Страница 16: ...to observe the following precautions associated with any heating appliance or open fire Do not cover or restrict the fireplace upper or lower vents in any way as this may result in a build up of hazar...

Страница 17: ...Copyright 17 Option 2 Three speed fan as additional option on SG units or EG units without remote controlled electronics eg units with on off hi low switches on the wall Option 1 Single speed fan as...

Страница 18: ...to the hi kPa value in the table for maximum output test point inlet Modulator Harness Connections 1 2 BSPT gas outlet SIT 840 Control Valve test point outlet 1 2 BSPT gas inlet adjustment screw After...

Страница 19: ...21 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 19 ON OFF SWITCH SIT 840 WIR...

Страница 20: ...crew B to Increase the Pressure and Screw it Out to Decrease the Pressure Carefully replace the Modulator Plas tic Cap Set the pressure to the hi kPa value in the table for maximum output The burner w...

Страница 21: ...1 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 21 HIGH LOW SWITCH SIT 845 WI...

Страница 22: ...Press and hold the or button for 2 seconds or longer to in crease or decrease the day of the week by 1 day every 0 5 seconds Press OK to complete setting The time and day of the week is now set SETTI...

Страница 23: ...WE TH FR MO TU WE TH FR SA SU SU SA MO TU WE TH FR SA SU To accept the selected day s of the week press OK First period s start time The display will indicate P1 on the top The Hour and AM PM settings...

Страница 24: ...Google Play Store https play google com store apps details id com millec intelligythermostatmkii For instructions on how to push the appliance to your Wi Fi please go to the Warmington website and fi...

Страница 25: ...irst and once this is on it will ignite the main burner Pressing and releasing the power button again will switch off the appliance When the appliance is turned on the gas fire will be set to medium f...

Страница 26: ...to pressure is to be carried out by a Certified Gasfitter If adjustments are necessary remove the cap The Pressure Adjustment screw and nut are on the front side of the Gas Control Valve shown in dia...

Страница 27: ...tisfied that the appliance is working correctly fit the front panel assembly back to the gas burner NOTE Ensure you peel the Protective Plastic Coating from any stainless steel components if fitted Al...

Страница 28: ...Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 28 FULLY MODULATING SIT 845 WI...

Страница 29: ...te building codes This appliance must be serviced annually and any service operation must be carried out by a qualified service person WARNINGS WARNING ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT B...

Отзывы: