14 June 2016 

Due to continued product improvement, Warmington Ind LTD reserves the right to change product specifications without prior notification. 

All Dimension are in mm 

Note: 

When the Base screw is removed, gas will leak from the out let, ensure that the pilot is not adjusted 

or the screw is removed when the fire is burning. 

 

Adjustment of Pilot - 3 Flame: Unscrew Base Screw  as shown in Diagram 2. 

 

Insert  a  Screw  Driver  as  shown  in  Diagram  3  and  adjust  the  Adjustment  Screw  up  inside  the  3 
Flame Pilot to adjust the Flame Height. 

 

The Flame must always be passing over the Electrodes &/or File Tube on either side. 

 

Replace the Base screw and check for leaks.   

ADJUSTMENT OF HI

LOW PRESSURE                       (SG ONLY)                      (Only to be Adjusted by Gasfitter)                            

 

ADJUSTMENT OF THE PILOT

3 FLAME                (BOTH SG & EG)                  (Only to be Adjusted by Gasfitter)   

 

Note*  Control Valves are Factory Set but may require adjustment onsite. 

Turn Appliance Off & Remove Front Plastic Cover on Igniter, Pull Cover to Slide off. 

Unscrew Test Nipple on the Burner Manifold & fit the Test Gauge Securely - See Diagram. 

* To Set the High: Light the Burner & turn to High - Then Adjust the High Screw to the Desired Pressure. See page 10 

* To Set the Low  Light the Burner & turn to Low - Then Adjust the Low Screw to the Desired Pressure. See page 10 

Extinguish Appliance, remove Test Equipment and Secure Test Nipple. 

* Check Valve & Burner for Correct Operation & check Fire for Gas Leaks. 

Adjustment of High & Low Settings Must be Carried out by a Certified Gas Fitter Only

3 Flame Pilot in 

Assembled State 

Correct Operation of 

3 Flame Pilot 

Note: to Gas Fitters

 

The 3 flame pilot may need adjustment 

after a period of running time on set up  
as  the  increase  in  heat  in  the  fire  will 

induce  a  higher  draft  in  the  fire,  and 
may  pull  in  flame  away  from  the  File 
Tube causing the fire to shut down.

 

Gas Test 
Nipple for 
SG Burners 

Содержание SG 700

Страница 1: ...ion The Warmington unit is to be installed by a certified Warmington installer or an approved NZHHA installation technician See www homeheat co nz members for a certified NZHHA SFAIT Installer in your...

Страница 2: ...on the pressure difference from inside the building to the outside A lower pressure in the building may induce a draft down the flue system and back into the building causing the fire to smoke or spil...

Страница 3: ...rner Width A 674 754 874 1074 Burner Height B 205 205 205 205 Burner Depth C 272 272 272 272 Flue Diameter Min J 200 200 250 250 Flue CSA mm K 31 416 31 416 49 087 49 087 WARMINGTON BURNERS NOTE IMPOR...

Страница 4: ...ctor Size mm 2 X 1 1mm 2 X 1 2mm 2 X 1 3mm 2 X 1 4mm Burner Pressure High kPa 2 5 2 5 2 5 2 5 Burner Pressure Low kPa 0 75 0 75 0 75 0 75 MJ h 29 38 42 50 Flame Effect Output Only Effect Effect Effect...

Страница 5: ...hat the Gas Type Specified on the Data Plate is correct for the available supply LPG or NG A Copper Gas supply capable of supplying the correct MJ h should be brought into the rear of the Installation...

Страница 6: ...roughest Face Outward Ensure Coal positioning does not directly block the 3 Flame Pilot The placement of the Coals Logs may vary to make an even Flame Pattern Logs and Twigs may be scattered to achie...

Страница 7: ...ng the Switch in a Depressed State repeat steps 2 3 if necessary Once the Pilot Flame is lit hold this position for 3 5 seconds release from the Depressed State before setting the Flame Control to Ful...

Страница 8: ...rol Valves are Factory Set but may require adjustment onsite Turn Appliance Off Remove Front Plastic Cover on Igniter Pull Cover to Slide off Unscrew Test Nipple on the Burner Manifold fit the Test Ga...

Страница 9: ...es on the principle of dual radiant and convected heat Therefore it is important to observe the following precautions associated with any heating appliance or open fire Do not cover or restrict the fi...

Страница 10: ...adjust to Low Flame and check pres sure NOTE If setting the Pressure is required it is to be carried out by a Certified Gas Fitter If adjustments are necessary remove the cap The Pressure Adjustment S...

Страница 11: ...serviced annually and any service operation must be carried out by a qualified service person WARNINGS WARNING ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING AU...

Отзывы: