Failure 

Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 94

Possible low gas pressure or 
exhaust recirculation

Boiler does not work, E94 
error code flashing on the 
screen 

> Gas inlet pressure LOW
> Recirculation on fluegas 
path
> Blokage on flue or wrong 
flue
> Aging or rust on the 
electrode
> Electrode position
> Combustion calibration
> Gas valve failiure
> Electronic board

1-) Call for authorised service at first
2-) Check wrong flue OR flue gas blockage 
3-) Check recirculation ( flue gas leak ) from flue gas path to fresh air 
side, check flue gas sealings specially
4-) Check any problems on the ionisation electrode, (like condensation, 
rust etc.), and control poistioning of the electrode, if electrode poistion 
wrong calibrate electrode according to user manual page 118 or 119
5-) Check combustion CO2 or O2 values on HI and LO mode at sweep-
er mode according to direction of manual page 67- 70   
6-) Perform Auto Calibration according to page 76 or 77
7-) if not successfull replace gas valve, and Perform Au-To calibration 
according to page 76 or 77   
8-) If fault still persists Replace board, but use original service key 
from the board dismantled to keep original parameters and calibration 
points. If original service key not used aslo adjust P15 releated to the 
default value of boiler power and perform Au-To calibration according 
to page 76 or 77   

Attention: Only authorised service must perform Au-To 

calibration

E 95

Intermittent combustion 
value

Boiler does not work, E95 
error code flashing on the 
screen 

> Harness on electrode and 
earth
> Aging or rust on the 
electrode
> Electrode position
> Combustion calibration

1-) Call for authorised service at first

E 96

Flue or air suction way 
blockage 

Boiler does not work, E96 
error code flashing on the 
screen 

> Blokage on flue
> Blokage on air suction path

1-) Call for authorised service at first

E 98

SW error, board start-up 
error fault

Boiler does not work, E98 
error code flashing on the 
screen 

> Boiler software problem

1-) Call for authorised service at first

E 99

Generic fault

Boiler does not work, E99 
error code flashing on the 
screen 

> Boiler electronic hardware 
problem

1-) Reset & Restart boiler 
2-) Call for authorised service at first

flashing 

LCD

Half Power mode on Lawa / 
Lawa Plus models

Boiler continue to work, 
flashing screen boiler still 
operational 

> Recirculation on fluegas 
path
> Blokage on flue or wrong 
flue
> Combustion calibration
> Temporary wind precence

1-) If there is strong wind (ie.wind storm) wait until the wind storm stop 
then keep using the boiler as it is 36 or 48 hours boiler try to remove 
half power mode by it self automatically by increasing power gradually.  
2-) IF problem persist after 48 hours Call for authorised service

(1) Call the Authorized Service if failure continues.
(2) 81 numbered failure corresponds any blocking in the exhaust gas pipe. In such case, you should consult the authorized service technician before 
restarting the combi.

4.2. RECOMMENDATIONS FOR ECONOMICAL USE 

OF COMBI 

Your combi is adjusted at ECO mode for economic use, we recommend not 
to change. 

Correct Capacity Selection

Heat loss calculation of the combi location should be made correctly and 
combi capacity should comply with this calculation. Devices not having 
adequate capacity shall give late responses to heating requests, devices 
with higher capacity may cause discomfort and more fuel consumption 
as they more frequently opened and closed. Therefore, combi capacities 
should be selected according to the place used. 
 

Insulation

Insulation of your building is the most important item reducing the heat loss 
and gas consumption. However, as your combi has the highest thickness 
insulation of its class, heat loss is minimized. 
 

Radiators

Ensure balancing our pressure distribution of your radiator installation 
within the house by making reduction adjustments from radiator valves.

Placing furnitures in front of radiators prevents air circulation and causes 
discomfort and more fuel consumption. Reducing radiator valves of rooms 
not used for a long period or if thermostatic radiator valve is used, bringing 
to the lowest position then, closing room doors will provide saving. 
 

Domestic Hot Water

Always adjust temperature of domestic hot water as low as possible.  
Adjustment of temperature adjuster as low ensures a considerable power 
saving. In addition, high domestic hot water temperatures cause strong 
calcification and that negatively affects operation of the device (for 
instance, longer heating periods, less flow rate). 
 

Thermostatic Radiator Valves

You can both ensure efficiency and comfort balancing the heat distribution 
around the house by using Thermostatic Radiator Valves. 
 

Room Thermostats

Your combi will operate more economically as you will have the chance to 
adjust requested room temperature according to comfort and economy 
timings via room thermostats. Thus, you can adjust temperature of your 
room as you wish, and also you can acquire approximately 6% power saving 
with every degree of temperature decrease. 

Содержание LAWA 18

Страница 1: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWA PLUS...

Страница 2: ...Lawa LawaPlus Enerwa E24 EnerwaPLUSE24...

Страница 3: ...2 2 16 Installation at Partially Protected Exteriors 12 2 2 17 Electrical Connections 12 2 2 18 Optional Controls Room Thermostat External Weather Temperature Sensor and Others 13 2 3 HYDRAULIC INSTA...

Страница 4: ...under any circumstances during installation use or maintenance operations and device warranty shall also be void Only the authorized Warmhaus Service is authorized to make the electrical connection o...

Страница 5: ...r matches Close valves of devices operating with natural gas and your gas meter Immediately evacuate the place with gas odour Natural Gas Emergency Line from your neighbour or another suitable place D...

Страница 6: ...lace Wall installation for the combi boiler should be well secured The hanger plate given as standard with the combi should be installed according to the technique to a full or semi full brick wall ac...

Страница 7: ...abnormal operations Various alloy layers may be formed during transit of LPG gas in tanks depending on mixture compositions That causes a change in heating power of mixture assigned to the device and...

Страница 8: ...er and by using elbows as low as possible At least 1 bar pressurized grid input water should be supplied to ensure adequate domestic hot water Hydrophore should be used if required Figure 10 Flue peri...

Страница 9: ...plications Each 45 elbow usage requires to decrease maximum 50 cm from horizontal vertical distance 60 100 Conventional 90 Elbow 153 11 660 600009 It can be used in horizontal and or vertical flue app...

Страница 10: ...elbow contacting with the restrictive set Place the External Wall Plate into the flue terminal as seen in Figure 11 12 for grouping the flue output terminal After placing the flue output terminal thr...

Страница 11: ...rd Flue Set Elbow 90 b Flue Extension Pipe c Additional 90 Elbow d Standard Flue Set Pipe Figure 16 II Two 90 elbow sample flue installations d a b c a b c d 4 m Figure 15 I Single 90 bended sample fl...

Страница 12: ...Hermetic Flue Type fire resistant insulation material is placed between the wall and exhaust gas relief pipe Materials used for manufacturing the combi are resistant against glycol and propylene based...

Страница 13: ...sockets and extension cables are not allowed to use 2 2 17 Optional Controls Room Thermostat External Weather Temperature Sensor and Others Room thermostat Outside Temperature Sensor etc control devi...

Страница 14: ...of the radiator Combi safety valve relief should be connected to a discharge cone Otherwise safety valve shall be activated and manufacturer shall not be responsible due to water discharge around the...

Страница 15: ...s valve radiator and tap water valves If you will shut off the combi for a short period perform below written operations Do not close combi electrical fuse gas valve radiator and tap water valves Leav...

Страница 16: ...screens consist of navy blue colored backlight LCD screen 2 buttons Radiator 3 and Hot Tap Water 4 and 2 pcs RESET 2 and MODE 1 pushbuttons RESET It is used for re starting the combi and eliminating t...

Страница 17: ...en light turns off At that position you can adjust the temperature between 35 80 C with the Radiator CH temperature adjustment button 3 Temperature value increases when button is rotated clockwise or...

Страница 18: ...if the pressure is lower than this value 18 Failure indicator The temperature value displayed on the combi screen has a 3 C tolerance depending on environmental conditions not arising from the combi...

Страница 19: ...installation Hold the MODE button for switching on the combi when letter is available on the screen A cycle starts on the screen Release the button when cycle is completed In some cases combi initiall...

Страница 20: ...er is seen as the screen screen light turns off your combi is now at STANDBY position Figure 31 Thermostat position Figure 32 Outside weather temperature sensor Figure 33 Outside temperature sensor op...

Страница 21: ...zed Service according to your request Air Discharge Function Activating the menu for LAWA PRIWA and ENERWA models Air discharge function can be activated by pressing the RESET button more than 5 secon...

Страница 22: ...ermittent contacts or open contacts on harness carefully 3 Check Domestic heating water temperature sensor ressistance 4 Check cabeling and connectors between NTC and board 5 Reset Restart boiler E 13...

Страница 23: ...vice at first E 42 Buttons anomaly Boiler does not work E42 error code flashing on the screen Wrong parameters settled on TsP menu 1 Call For service E 43 Opentherm communication error Boiler does not...

Страница 24: ...st perform Au To calibration E 78 Max regulation current value reached Boiler does not work E78 error code flashing on the screen Gas inlet pressure Aging or rust on the electrode Recirculation on flu...

Страница 25: ...Au To calibration E 88 Fault of electronic gas valve managing circuit Boiler does not work E88 error code flashing on the screen Cabeling disconnections Gas valve failiure 1 Call for authorised servi...

Страница 26: ...ration Temporary wind precence 1 If there is strong wind ie wind storm wait until the wind storm stop then keep using the boiler as it is 36 or 48 hours boiler try to remove half power mode by it self...

Страница 27: ...ailures occurring due to transportation unloading loading storing external physical Crushing scratches fractures and chemical factors following delivery of the product 6 Damages and failures arising f...

Страница 28: ...10 7 28 10 32 5 12 8 Max Domestic Hot Water flow rate t 30 C min 10 5 10 9 10 7 10 9 13 9 13 3 13 9 14 2 Maximum Minimum water pressure bar 10 0 3 10 0 3 10 0 3 10 0 3 Temperature adjustment range oC...

Страница 29: ...2ELL I 2H I3P NUMBER OF CHOOSED CONNECTING CONDITIONS Used gas G20 G20 G25 G25 G20 G25 G20 G31 Countries of destination AT BG CH CZ DK EE ES FI GB GR IE IT LT LV NO PT RO SE SI SK DE LU PL RO BE FR NL...

Страница 30: ...30 warmhaus com...

Страница 31: ...been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject...

Страница 32: ...CONVENTIONAL COMBI BOILERS INSTALLATION USER MANUAL LAWA LAWA PLUS Instruction booklet code of Lawa LawaPlus 150 11 606 000004 Revision Date 09 2020...

Отзывы: