1.2.  COMBI INSTALLATION RULES

1.2.1. General Rules for Installation Places of Combi Boilers

No restriction is available for places where Hermetic (C typ) combi is installed 
(devices may be installed regardless the room volume and ventilation type). 
Also, they may be installed at partially protected areas such as balcony, 
terrace provided that being placed in protective cabinets and taking required 
precautions against frost of installation water.

Combi should be soundly installed to building wall. Flexible connection 
piece should be used between the combi and gas line. Flex lengths to be 
used in A, B and C type devices should not exceed dimensions allowed by 
local gas authorities. Flue outputs of hermetic combis must be connected to 
places open to exterior and having air circulation. Installation (positions of 
pipe output opening based on various forms, vertical, horizontal minimum 
distances, cross section areas of channels if given to channels, etc.) must 
be carried out according to regulation standards, current legislation and 
in compliance with local technical regulations and the required technical 
procedures. 

1.2.2. Places Not Suitable for Installing Hermetical Combi Boilers

Stairways of Buildings,
• Corridors available for general use, ventilation ways and shafts, lofts, attics, 

emergency exit doors, cellars, hall and similar places creating common use 
areas,

• Yards between buildings,
• Narrow cornice distances,
• Over flue walls,
• Enclosed balconies,
• Open balconies (except being located in the cabinet and permission of the 

device company),

• Below protruding structure parts preventing exhaust gas output,
• Places those may be directly subjected to wind resistance,
• It is forbidden to install Hermetic combi (C type) to openings providing

clean air to other units!

1.2.3. Wall Installation of Combi and Selecting the Installation Place

•  It should be controlled and ensured that the wall installation of the combi 

is sound and reliable.

• The hanger plate given as standard with the combi should be installed

according to the technique to full or semi-full brick wall according to

installation scheme and with connection screws and not to be used for 
other purposes.

• In case of using different materials for installation, combi shall be out of

the warranty scope.

• If the wall of installation is not a brick wall, initially the reliability of support 

system should be controlled.

• Combi should be installed on a wall resistant to fire.
• NOTICE: Combustible and corrosive materials:
• Chemically aggressive substances can corrode the appliance and

invalidate any guarantee.

• Do not store or use any combustible materials (paper, thinners, paints,

propellants, cleaning agents etc.) Keep the distance minimum 50 mm.

• Inside the cupboard containing the appliance or within the vicinity of the

appliance.

• 1,8 - 2,2 m height is recommended for installation of the combi hanger

plate.

• For places with limited installation place, combi should be installed

at minimum 30 cm height from ground and by leaving at least 5 cm
distances from both sides in order to allow easy intervention of the service 
technician.

• Combi installation must not performed in environments containing

explosive, flammable substances and acid fumes

• Installation cannot be made at near or on ovens, radiators or heater

devices.

• Hermetic combis can be installed in furnitures but at least 5 cm each

should be left at both sides.

• If to be installed on the kitchen table or the set, at least 30 cm   distance

should be left under the combi.

• It is recommended to connect the output to drain line with a transparent

hose against the possibility of water leakage from Safety Valve of combi
during installation. If this is not possible; do not place electronic devices,
delicate, corrodible devices, components and tools under the combi.

• Do not place/use any furnitures below the combi due to above mentioned 

reasons.

Make sure that there are no liquids or inflammable materials in the 
immediate vicinity of the boiler.
It is necessary to leave a spesific distance 1.0  mt between the 

heating device and the building material containing combustible material 
even the maximum allowable temperature value of 85 °C in the rated heat 
capacity of the appliance is not exceeded.

Figure 6 

Boiler minimum dimensions in the cabinet *Minimum clearances required for servicing

Содержание EWA 20

Страница 1: ...CONDENSING COMBI BOILER INSTALLATION MANUAL EWA 20 EWA 24...

Страница 2: ...EWA 20 EWA 24...

Страница 3: ...n Case of Using Bottled Gas 9 Filling the siphon for Condensation Line 10 Installation at Partially Protected Exteriors 10 Electrical Connections 10 Optional Controls Room Thermostat Outside Sensor an...

Страница 4: ...4 warmhaus com...

Страница 5: ...ilable BE FR YES II 2H3B P Natural Gas 20 mbar G20 Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available DE YES II 2ELL3B P Natural Gas 20 mbar G20 Ava...

Страница 6: ...6 warmhaus com...

Страница 7: ...Figure 2 User s Guide Figure 5 Exhaust gas flue set 471 1000 GAS G3 4 G3 4 G3 4 80 mm 65 mm 65 mm 64 mm 725 mm 592 mm 422 mm G1 2 G1 2 75 mm 73 mm 110 m m 114 mm OPTIONAL Ewa Priwa ERP Priwa ERP Plus...

Страница 8: ...r semi full brick wall according to installation scheme and with connection screws and not to be used for other purposes In case of using different materials for installation combi shall be out of the...

Страница 9: ...1 2 7 In Case of Using LPG Tank LPG use is recommended for heat requirements over 24 kW New LPG stock tanks may contain settled gas residues nitrogen however that pauperises the mixture assigned to t...

Страница 10: ...able to use gas and water connection pipes for earthing WARMHAUS A cannot be held as responsible for any damages and losses on individuals or commodities arising from failing to provide earth connecti...

Страница 11: ...nsor is activated when connected as independent from the used room thermostat typology and functions as common with room thermostats The relation between installation input temperature and exterior we...

Страница 12: ...0 600021 WT RF03 Large Screen Modulated Weekly Program Scheduled Wireless room thermostat Product code 153 11 660 600022 150 cm Min 30 cm Room thermostat shall be mounted 1 25 to 1 5 m above the groun...

Страница 13: ...d in the hot tap water Hydrophore should be used if required Prior to filling the radiator installation it must be flushed and all wastes must be cleaned Warning In order to prevent invalidity of devi...

Страница 14: ...mum 3 storey buildings Drainage and Ventilation Pipe Min 19 mm Water Air proof insulation Figure 2 26 Connection of condensate Drainage Pipe to External Soil Vent Stack Connection of Condensate Draina...

Страница 15: ...thorized service appointment request Gas opening approval certificate should be taken from the local gas company for your gas line Combi electricity connection should be made via 2 or 3 Amps fuse Figu...

Страница 16: ...o be used in exhaust gas installation of hermetic combi should be original Warmhaus flue sets and they should be used by considering measurements and restrictions given in installation instructions In...

Страница 17: ...ontent 10 00 tolerance 0 5 0 5 maximum allowable draught and maximum allowable pressure difference between combustion air inlet and flue gas outlet including wind pressures 120 Pa characteristics and...

Страница 18: ...temperature for dimensioning the common duct system shall be declared as 25 C c the combustion product mass flow rate at maximum heat input shall be specified for every connection point the terminal...

Страница 19: ...H C R A I J K I L S B T U Likely flue positions requiring a flue terminal guard Figure 32 Environmental locations of flue Terminal Position with Minimum Distance mm A1 Directly below an opening air br...

Страница 20: ...tion hatch edge must not be fitted more than 1 5 meters away from a flue joint Inspection hatches should be fitted at every change of direction Flue Data 60 100mm Concentric flue systems information W...

Страница 21: ...ceed 10 m with single elbow horizontally Also this total length reduces by 1 m with every 90 elbows or two 45 elbows Maximum 3 pieces of 90 elbow can be used a Standard Flue Set Elbow 90 b Flue Extens...

Страница 22: ...es Flue Data WARNING Warmhaus flue pipe technical specification Vertical Termination Maximum length 11 meters including the bend or adaptor connected directly to the boiler Effective flue length for t...

Страница 23: ...al flue set installation application Implementation L1 0 3 m L2 0 5 m 45 elbow equivalent length L3 2 0 m L4 0 5 m 45 elbow equivalent length L5 1 0 m L6 1 5 m L Total 6 3 m 6 3 m Lmax 11 m Correct in...

Страница 24: ...ension of 140 mm see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour...

Страница 25: ...0 Condensing Flue Extension L 1000 mm 15311660600015 White 60 100 Condensing Flue Extension L 2000 mm 15311660600016 White 60 100 Condensing 45 Elbow 15311660600017 White 60 100 Condensing 90 Elbow L...

Страница 26: ...0 mm 80 mm L 500 mm 153 11 660 600091 80 Condensing Twin Flue Extension Pipe L 1000 mm 80 mm L 1000 mm 153 11 660 600092 80 Condensing Twin Flue Extension Pipe L 2000 mm 80 mm L 2000 mm 153 11 660 600...

Страница 27: ...n products will not cause a nuisance and that the terminal will not obstruct the passageway 3 If a terminal is less than 2 metres above a balcony above ground or above a at roof to which people have a...

Страница 28: ...NTC 4 Check cabling and connectors between double NTC and board 5 Reset Restart boiler E 06 No ignition Boiler does not work E06 error code flashing on the screen Gas supply failure 1 RESET boiler che...

Страница 29: ...ault Boiler does not work E12 error code flashing on the screen Domestic heating water temperature sensor in storage tank faulty 1 Check intermittent contacts or open contacts on harness carefully 2 C...

Страница 30: ...ed 2 Check the root cause of Error code to solve 3 If fault still persists call for authorised service E 37 Low voltage anomaly Boiler does not work E37 error code flashing on the screen Low voltage 1...

Страница 31: ...onnections Combustion calibration Electronic board Gas valve failiure 1 Call for authorised service at first 2 Check gas supply pressure must be 20 17 mbar Gas pressure must be in between on this valu...

Страница 32: ...ulation flue gas leak from flue gas path to fresh air side check flue gas sealings specially 5 Check any problems on the ionisation electrode like condensation rust etc and control poistioning of the...

Страница 33: ...e electrode 5 Check for condensation on the cabling AND OR on board 6 Check earth connection between board and electrode 7 Check electrode cabeling between board and electrode 8 Check combustion CO2 o...

Страница 34: ...sed service must perform Au To calibration E 96 Flue or air suction way blockage Boiler does not work E96 error code flashing on the screen Blokage on flue Blokage on air suction path 1 Call for autho...

Страница 35: ...omestic Hot Water Circuit Water Heating Energy Efficiency Class A A A Water Heating Declared Load Profile XL L XL Water Heating Energy Efficiency 85 81 84 Gas Consumption at Maximum m h 2 47 2 83 0 73...

Страница 36: ...Heating Energy Efficiency s 91 92 92 Useful efficiency at rated heat output and high temperature regime 2 4 87 60 87 57 87 57 Useful efficiency at 30 of rated heat output and low temperature regime 1...

Страница 37: ...arefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject to our...

Страница 38: ...EWA 20 EWA 24 CONDENSING COMBI BOILER INSTALL ATION MANUALEwa Installation Service Manual Code 15011606000140 Revision Date R00 12 2021...

Отзывы: