Error Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 94

Possible low gas pressure 
or exhaust recirculation

Boiler does not work, E94 
error code flashing on the 
screen 

> Gas inlet pressure LOW
> Recirculation on fluegas 
path
> Blokage on flue or wrong 
flue
> Aging or rust on the 
electrode
> Electrode position
> Combustion calibration
> Gas valve failiure
> Electronic board

1-) Call for authorised service at first
2-) Check wrong flue OR flue gas blockage 
3-) Check recirculation ( flue gas leak ) from flue gas path to fresh air 
side, check flue gas sealings specially
4-) Check any problems on the ionisation electrode, (like condensation, 
rust etc.), and control poistioning of the electrode, if electrode poistion 
wrong calibrate the electrode.
5-) Check combustion CO2 or O2 values on HI and LO mode at sweeper 
mode. 
6-) Perform Auto Calibration.
7-) if not successfull replace gas valve, and Perform Au-To calibration. 
8-) If fault still persists Replace board, but use original service key 
from the board dismantled to keep original parameters and calibration 
points. If original service key not used aslo adjust P15 releated to the 
default value of boiler power and perform Au-To calibration. 

Attention: Only authorised service must perform Au-To calibration

E 95

Intermittent combustion 
value

Boiler does not work, E95 
error code flashing on the 
screen 

> Harness on electrode and 
earth
> Aging or rust on the 
electrode
> Electrode position
> Combustion calibration

1-) Call for authorised service at first
2-) Check intermittent contacts on harness carefully
3-) Check any problems on the ionisation electrode, (like condensation, 
rust etc.), and control poistioning of the electrode, if electrode poistion 
wrong calibrate the electrode.
4-) Check for condensation on the cabling AND/OR on board
5-) Check earth connection between board and electrode
6-) Check electrode cabeling between board and electrode
7-) Check combustion CO2 or O2 values on HI and LO mode at sweeper 
mode. 
8-) Perform Au-To calibration.

Attention: Only authorised service must perform Au-To calibration

E 96

Flue or air suction way 
blockage 

Boiler does not work, E96 
error code flashing on the 
screen 

> Blokage on flue
> Blokage on air suction 
path

1-) Call for authorised service at first
2-) Check wrong flue OR flue gas blockage 
3-) Check recirculation ( flue gas leak ) from flue gas path to fresh air 
side, check flue gas sealings specially
4-) Check venturi inlet if its blocked
5-) Check any blockage between fan and burner 
6-) Check combustion CO2 or O2 values on HI and LO mode at sweeper 
mode. 
7-) Perform Auto Calibration.

Attention: Only authorised service must perform Au-To calibration

E 98

SW error, board start-up 
error fault

Boiler does not work, E98 
error code flashing on the 
screen 

> Boiler software problem

1-) Call for authorised service at first
2-) Replace board direcly, adjust P15 releated to the default value of 
boiler power
3-) Perform Au-To calibration. 

Attention: Only authorised service must perform Au-To calibration

E 99

Generic fault

Boiler does not work, E99 
error code flashing on the 
screen 

> Boiler electronic 
hardware problem

1-) Call for authorised service at first
2-) Replace board direcly, adjust P15 releated to the default value of 
boiler power
3-) Perform Au-To calibration.
4-) if not successfull replace gas valve, and perform Au-To calibration. 

Attention: Only authorised service must perform Au-To calibration

f l a s h i n g 
LCD

Half Power mode on Lawa / 
Lawa Plus models

Boiler continue to work, 
flashing screen boiler still 
operational 

> Recirculation on fluegas 
path
> Blokage on flue or wrong 
flue
> Combustion calibration
> Temporary wind 
precence

1-) If there is strong wind (ie.wind storm) wait until the wind storm stop 
then keep using the boiler as it is 36 or 48 hours boiler try to remove 
half power mode by it self automatically by increasing power gradually. 
2-) IF problem persist after 48 hours Call for authorised service
3-) Check wrong flue OR flue gas blockage 
4-) Check recirculation ( flue gas leak ) from flue gas path to fresh air 
side, check flue gas sealings specially
5-) Activate service man menu and dis activate to remove half power 
mode
6-) IF problem still persist then perform Auto Calibration 
Attention: Only authorised service must perform Au-To calibration

Содержание EWA 20

Страница 1: ...CONDENSING COMBI BOILER INSTALLATION MANUAL EWA 20 EWA 24...

Страница 2: ...EWA 20 EWA 24...

Страница 3: ...n Case of Using Bottled Gas 9 Filling the siphon for Condensation Line 10 Installation at Partially Protected Exteriors 10 Electrical Connections 10 Optional Controls Room Thermostat Outside Sensor an...

Страница 4: ...4 warmhaus com...

Страница 5: ...ilable BE FR YES II 2H3B P Natural Gas 20 mbar G20 Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available DE YES II 2ELL3B P Natural Gas 20 mbar G20 Ava...

Страница 6: ...6 warmhaus com...

Страница 7: ...Figure 2 User s Guide Figure 5 Exhaust gas flue set 471 1000 GAS G3 4 G3 4 G3 4 80 mm 65 mm 65 mm 64 mm 725 mm 592 mm 422 mm G1 2 G1 2 75 mm 73 mm 110 m m 114 mm OPTIONAL Ewa Priwa ERP Priwa ERP Plus...

Страница 8: ...r semi full brick wall according to installation scheme and with connection screws and not to be used for other purposes In case of using different materials for installation combi shall be out of the...

Страница 9: ...1 2 7 In Case of Using LPG Tank LPG use is recommended for heat requirements over 24 kW New LPG stock tanks may contain settled gas residues nitrogen however that pauperises the mixture assigned to t...

Страница 10: ...able to use gas and water connection pipes for earthing WARMHAUS A cannot be held as responsible for any damages and losses on individuals or commodities arising from failing to provide earth connecti...

Страница 11: ...nsor is activated when connected as independent from the used room thermostat typology and functions as common with room thermostats The relation between installation input temperature and exterior we...

Страница 12: ...0 600021 WT RF03 Large Screen Modulated Weekly Program Scheduled Wireless room thermostat Product code 153 11 660 600022 150 cm Min 30 cm Room thermostat shall be mounted 1 25 to 1 5 m above the groun...

Страница 13: ...d in the hot tap water Hydrophore should be used if required Prior to filling the radiator installation it must be flushed and all wastes must be cleaned Warning In order to prevent invalidity of devi...

Страница 14: ...mum 3 storey buildings Drainage and Ventilation Pipe Min 19 mm Water Air proof insulation Figure 2 26 Connection of condensate Drainage Pipe to External Soil Vent Stack Connection of Condensate Draina...

Страница 15: ...thorized service appointment request Gas opening approval certificate should be taken from the local gas company for your gas line Combi electricity connection should be made via 2 or 3 Amps fuse Figu...

Страница 16: ...o be used in exhaust gas installation of hermetic combi should be original Warmhaus flue sets and they should be used by considering measurements and restrictions given in installation instructions In...

Страница 17: ...ontent 10 00 tolerance 0 5 0 5 maximum allowable draught and maximum allowable pressure difference between combustion air inlet and flue gas outlet including wind pressures 120 Pa characteristics and...

Страница 18: ...temperature for dimensioning the common duct system shall be declared as 25 C c the combustion product mass flow rate at maximum heat input shall be specified for every connection point the terminal...

Страница 19: ...H C R A I J K I L S B T U Likely flue positions requiring a flue terminal guard Figure 32 Environmental locations of flue Terminal Position with Minimum Distance mm A1 Directly below an opening air br...

Страница 20: ...tion hatch edge must not be fitted more than 1 5 meters away from a flue joint Inspection hatches should be fitted at every change of direction Flue Data 60 100mm Concentric flue systems information W...

Страница 21: ...ceed 10 m with single elbow horizontally Also this total length reduces by 1 m with every 90 elbows or two 45 elbows Maximum 3 pieces of 90 elbow can be used a Standard Flue Set Elbow 90 b Flue Extens...

Страница 22: ...es Flue Data WARNING Warmhaus flue pipe technical specification Vertical Termination Maximum length 11 meters including the bend or adaptor connected directly to the boiler Effective flue length for t...

Страница 23: ...al flue set installation application Implementation L1 0 3 m L2 0 5 m 45 elbow equivalent length L3 2 0 m L4 0 5 m 45 elbow equivalent length L5 1 0 m L6 1 5 m L Total 6 3 m 6 3 m Lmax 11 m Correct in...

Страница 24: ...ension of 140 mm see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour...

Страница 25: ...0 Condensing Flue Extension L 1000 mm 15311660600015 White 60 100 Condensing Flue Extension L 2000 mm 15311660600016 White 60 100 Condensing 45 Elbow 15311660600017 White 60 100 Condensing 90 Elbow L...

Страница 26: ...0 mm 80 mm L 500 mm 153 11 660 600091 80 Condensing Twin Flue Extension Pipe L 1000 mm 80 mm L 1000 mm 153 11 660 600092 80 Condensing Twin Flue Extension Pipe L 2000 mm 80 mm L 2000 mm 153 11 660 600...

Страница 27: ...n products will not cause a nuisance and that the terminal will not obstruct the passageway 3 If a terminal is less than 2 metres above a balcony above ground or above a at roof to which people have a...

Страница 28: ...NTC 4 Check cabling and connectors between double NTC and board 5 Reset Restart boiler E 06 No ignition Boiler does not work E06 error code flashing on the screen Gas supply failure 1 RESET boiler che...

Страница 29: ...ault Boiler does not work E12 error code flashing on the screen Domestic heating water temperature sensor in storage tank faulty 1 Check intermittent contacts or open contacts on harness carefully 2 C...

Страница 30: ...ed 2 Check the root cause of Error code to solve 3 If fault still persists call for authorised service E 37 Low voltage anomaly Boiler does not work E37 error code flashing on the screen Low voltage 1...

Страница 31: ...onnections Combustion calibration Electronic board Gas valve failiure 1 Call for authorised service at first 2 Check gas supply pressure must be 20 17 mbar Gas pressure must be in between on this valu...

Страница 32: ...ulation flue gas leak from flue gas path to fresh air side check flue gas sealings specially 5 Check any problems on the ionisation electrode like condensation rust etc and control poistioning of the...

Страница 33: ...e electrode 5 Check for condensation on the cabling AND OR on board 6 Check earth connection between board and electrode 7 Check electrode cabeling between board and electrode 8 Check combustion CO2 o...

Страница 34: ...sed service must perform Au To calibration E 96 Flue or air suction way blockage Boiler does not work E96 error code flashing on the screen Blokage on flue Blokage on air suction path 1 Call for autho...

Страница 35: ...omestic Hot Water Circuit Water Heating Energy Efficiency Class A A A Water Heating Declared Load Profile XL L XL Water Heating Energy Efficiency 85 81 84 Gas Consumption at Maximum m h 2 47 2 83 0 73...

Страница 36: ...Heating Energy Efficiency s 91 92 92 Useful efficiency at rated heat output and high temperature regime 2 4 87 60 87 57 87 57 Useful efficiency at 30 of rated heat output and low temperature regime 1...

Страница 37: ...arefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject to our...

Страница 38: ...EWA 20 EWA 24 CONDENSING COMBI BOILER INSTALL ATION MANUALEwa Installation Service Manual Code 15011606000140 Revision Date R00 12 2021...

Отзывы: