WarmFlo HD320 Скачать руководство пользователя страница 20

1/8/2008 1  HD320 

E

E

l

l

e

e

c

c

t

t

r

r

o

o

-

-

H

H

E

E

L

L

P

P

S

S

 

 

I

I

V

V

 

 

WarmFlo Terminology, Key Terms 

 

ST

 – supply temperature sensor.  This is the warm air or duct sensor (boiler – supply outlet 

water). 
 

OT 

– outdoor temperature sensor.  Provides the WarmFlo board with outdoor temperature 

information. 
 

DT

 – desired temperature to overcome building heat loss, the diagonal line on heat loss curve.  

The front panel efficiency knob selects one of 8 curves to determine DT at specific real time OT. 

 
DT Flat 

– this is an internal reference point, as WarmFlo establishes this mode it in essence sets 

the operating point at 125° F. (Analyzer or software may have any value from 123 to 125). 
Electric element modulation and staging are still in effect. The staging will be based upon the ST 
sensor detecting and operating around the 125° point. 
 

Note

: All four stages do not automatically go to full on. 

 

HL

 – actually this is the same as “DT Flat”.  This perceived hi-limit temperature value (130°) 

within the control logic, measured by the ST.  This is over and above the 155° probe or 170° 
mechanical hi-limits. 
 

Full electric (or Full EL)

 – this setting causes the modulation and staging to operate at “DT 

Flat”.  When first selected or turned on, the WarmFlo logic may first go through a process of 
building up to the “DT Flat” value.  Do not expect the outlet temperature to immediately jump up 
to this highest value.  However, on consecutive thermostat calls it will immediately step to the 
“DT Flat” temperature value. 
 

Note

: This is essentially the same as DT Flat and again all four stages do not 

automatically go to full on. 

 

Staging Disable Temperature – 

in all OT active sensor applications (DT cal) there is a setup 

program temperature to "hold off" each stage for warmer heating conditions. In other words, the 
OT sensor must be reporting a temperature below these values before the stage is allowed to 
come on. In WarmFlo Analyzer or PC software terminology this is called – STG1 DIS, etc. 
 
The stage-up situation relating to all of the above "DT Flat" operation is controlled by these stage 
enable temperature set points. This statement must be carefully related to all of the above. 

-

 

In other words, if the OT is reading 42° and the front panel is set to "full electric" the ST 
is looking to operate at 125°, but only stage 1 will be on. 

 
If for heat pump applications Stg 1 is set at 50°, there will be no electric element or standby 
furnace above 50° OT. 
 

Note

: For HP roomstat multi-wire thermostat application, the OT temp. set point must be 

below normal desired cooling. 

 

E tab (board top center)

 – in most WarmFlo products and TS Series boiler products there is a 

troubleshooting tab marked "E". When applying 24-volt (or jumpered to "W" tab) this input 
function immediately forces all four stages on and bypasses all temperature sensing or element 
modulation sequences.  If used verify blower also functions properly. 

Содержание HD320

Страница 1: ...onditioning The warm air dial suggested setting is 96 or 100 and the front dial selects the rate of ramp up or temperature increase based upon outdoor The C setting will provide 114 warm air at 0 or 1...

Страница 2: ...tor 1 General Comments 2 Application 3 Installation Requirements 5 Mechanical Installation 6 Electrical Installation 8 Setup or Programming 11 Operation Indicators 13 Handheld Analyzer Laptop Software...

Страница 3: ...or temperature Depending upon setup selection the moderate heating blower speed could be as low as 60 of full capacity and full capacity blower is only used below 15 outdoor Heat cool conventional or...

Страница 4: ...ing Utility Load Control Provisions are included for the Utility Receiver to interrupt compressor and WarmFlo or strip heat No provisions for dual heat add HP 5046 Two Speed Heat Pump Add WF HP2 inter...

Страница 5: ...e details several product types Re verify nameplate on your received unit to make sure it properly represents the product type you need for your installation application The setup control board jumper...

Страница 6: ...e ECM motor is approximately 120 F Specification Chart Model Number HE H 10 21 HE H 15 21 HE H 20 21 Cabinet Width 21 21 21 kW rating 10 15 20 Btu h 34000 51000 68000 Voltage Phase 240 1 240 1 240 1 C...

Страница 7: ...fety features and controls 2 If this is a Dual Heat system this product relates only to the addition to the furnace ducting system external to the gas or oil force air furnace The owner installer assu...

Страница 8: ...circulation through a filter at this Electric Furnace inlet you may need to have a slight restriction in order for the blower motor to arrive at its setup speed All transitions must have a slope of 3...

Страница 9: ...il must be at the bottom of the blower in order for WarmFlo to properly add temperature to the heat pump output Electro inlet cabinet is ideal for using a heat pump A coil NC805 This factory available...

Страница 10: ...motor accordingly Before tightening motor mount clamp be sure the blower wheel is properly centered inside the blower housing Electrical Installation WARNING TO AVOID THE RISK OF ELECTRIC SHOCK OR DEA...

Страница 11: ...may pick up too much shading and winds but the south side should be avoided unless there is a position which will shade the sun Install bracket with the sensor tip up cable downward Use care in selec...

Страница 12: ...connected to the tab Y1 Room Thermostat Heat Pump Single Stage You must use a basic HP stat with built in reversing valve function Typically this will be 6 wires A conventional heat cool 4 wire thermo...

Страница 13: ...the OT sensor must be below these values before the appropriate stage will come on This is independent of the supply sensor requirement Stage OT Temp 1 90 F 2 38 F 3 36 F 4 34 F WarmFlo Dial Settings...

Страница 14: ...ovides ramp up However instead of working with settings B and C common with heat pumps it may be okay to work with C or D for straight resistance Heat Loss Curve Within the brain of the WarmFlo contro...

Страница 15: ...tat cool jumper relates to heating and cooling Heat jumper is non active A 3 3 5 ton 1200 CFM B 2 5 3 ton 1100 CFM C 2 2 5 ton 1000 CFM D 2 ton 900 CFM Heat Pump When using a heat pump thermostat sele...

Страница 16: ...ll 1200 CFM SPD B The full speed blower action continues to the end of the thermostat cycle independent of any change at the ST or OT Room Thermostat Fan On Mode This sets up continuous air at 50 of t...

Страница 17: ...eset Simply turn off the 24 volt source power probably furnace or Electric Furnace circuit breaker when the green LED goes out count to 10 and re energize power supply 2 The terminal blocks for contro...

Страница 18: ...e hard to predict an error function A blinking green light may or may not be experienced Typically the cable is too long wrong type of sensor wire or some electrical interference on the sensor cable 2...

Страница 19: ...ECM Motor H C and HP Stat WFPDC5632 PCB Power Sup AC to DC 5850 Motor HP ECM GE 5541 Transformer 120 240 24 40VA 4038 Triac SSR 50 amp 24VDC 5127 Relay NO 25A 277 24VDC Coil 6630 Limit O 150 O 180 25A...

Страница 20: ...immediately jump up to this highest value However on consecutive thermostat calls it will immediately step to the DT Flat temperature value Note This is essentially the same as DT Flat and again all f...

Страница 21: ...ture However this also means you will be short cycling the HP compressor during other heat calls The maximum run time for the compressor is then about 30 minutes at any time of the day or at any parti...

Страница 22: ...y mode see previous section there is a 5 minute timer which begins at each heat call If after the 5 minutes the ST sensor is less than 80 the logic board itself goes into an automatic reset and restar...

Страница 23: ...various wiring arrangements for ECM variable speed blower Using E tab with HP stat emergency output see previous E tab section for blower operation caution Bad sensor safety if the internal logic dete...

Страница 24: ...not affect any altered reprogrammed functions It is smart enough to know it is no longer the original chip and that specific physical board from this time forward must be under the control of the PC s...

Страница 25: ...device that delivers greater than 100 this system can only deliver greater than 100 if it s running let it run Because of WarmFlo s design concept and its internal brain the heat loss curve diagonal...

Страница 26: ...ency knob setting is based upon comfort and efficiency The lower the setting the higher the overall operating annual efficiency the higher the setting the warmer the air at the register Chip code fiel...

Страница 27: ...al applications the installer furnished coil must have proper drip pan Access holes for refrigerant lines need to be cut in as required HE ICC 21 Hydronics Coil and Cabinet Depending upon capacity siz...

Страница 28: ...COOL D C B A CS UPCB6707 PWR ECM BLUE BLU WHT BK OUTDOOR UNIT DF W1 Y1 HEAT COOL RV LOGIC HI C RV O R Y Y2 COM VAC 24 HEAT COOL R W G Y Y2 C Y1 BK E G O ROOM THERMOSTAT HP Y 8 0 70 60 5 0 8 0 70 60 5...

Страница 29: ...A CS UPCB6707 PWR ECM BLUE BLU WHT BK OUTDOOR UNIT DF W1 Y1 HEAT COOL RV LOGIC HI C RV O R Y Y2 COM VAC 24 HEAT COOL R W G Y Y2 C Y1 BK E G O ROOM THERMOSTAT HP Y R SET JUMPER TO HEAT COOL BLUE NOTES...

Страница 30: ...1 Y1 HEAT COOL RV LOGIC HI C RV O R Y Y2 COM VAC 24 HEAT COOL R W G Y Y2 C Y1 BK E G O ROOM THERMOSTAT HP Y SET JUMPER TO HP BLUE NOTES 1 SEE MODEL SPECIFICATIONS TABLE FOR RATINGS FOR SINGLE FEED USE...

Страница 31: ...50 F 150 F HL3 150 F HL2 150 F HL1 CB1 L2 L1 CB2 L2 L1 CB1 L1 CB1 L2 CB2 L1 CB2 L2 BK BK BK BK R R R R BK BK BK BK HECBW5844 HECBW5844 L1 L1 L1 L1 CB2 L2 CB2 L1 CB1 L2 CB1 L1 CB2 L1 CB1 L2 CB1 L1 L2 L...

Страница 32: ...EMENT HL HI LIMIT K RELAY M MOTOR BLOWER PC CIRCUIT BOARD T TAB TERMINAL SC SCREW TERMINAL L1 L1 L2 L2 CB1 L1 CB1 L2 CB2 L1 CB1 L1 CB1 L2 CB2 L1 L1 L1 L1 HECBW5844 HECBW5844 BK BK BK R R R BK BK BK CB...

Страница 33: ...5 NW823 R BR GY BL VI Y YG W BKW WBK 4 3 2 1 J2 5 6 7 8 9 10 E2 E1 150 F HL2 150 F HL1 CB1 L2 L1 CB1 L1 CB1 L2 BK BK R R BK BK HECBW5844 HECBW5844 L1 L1 CB1 L2 CB1 L1 CB1 L2 CB1 L1 L2 L2 L1 L1 COMPONE...

Страница 34: ......

Страница 35: ......

Страница 36: ...e by Electro Industries or its authorized representative Electro Industries will cover reasonable labor costs to repair defective product or product parts for ninety 90 days after installation TWENTY...

Страница 37: ...n the installation and instruction manual and all state and federal codes and statutes If not the warranty will be null and void 4 The purchaser shall have maintained the product in accordance with th...

Отзывы: