warema_866217_alhb_en_v6•2022-07-01
We reserve the right to make technical modifications
2
Function
Momentary-contact switches or latched switches can be
used as floor operating elements. The move commands
of the floor switches are passed on directly to the motor
control units.
The operating elements may not be jumpered.
For the use of momentary contact switches as floor
switches this means:
The operator has to press the floor momentary-contact
switch until the sunblinds of the controlled facade have
reached the desired position.
A move command from a higher-level central control
takes precedence over the floor momentary-contact
switch.
For the use of latched switches as floor switches this
means:
The operator presses the floor latched switch and
moves away from the operating point. The sunblinds
move UP or DOWN to the end position.
A move command from a higher-level central control
takes precedence over the floor latched switch. The
sunblinds move in the direction specified by the central
control exactly as long as the central command remains
active. Afterwards the sunblinds move again into the
end position specified by the latched floor switch.
When the floor latched switches are latched, the local
switches of the motor control unit are blocked
Commissioning
The device is ready for operation after the installation has
been completed and the operating voltage applied.
Maintenance
There are no parts within the device that require mainte-
nance. In the event of a malfunction, the installed miniature
fuse may only be exchanged by a certified electrician.
Cleaning
Clean the housing with a soft, dry cloth. Do not use deter-
gents, cleaning agents, solvents, abrasive substances or
steam cleaners!
Liability
Failure to comply with the product information contained in
these instructions and any use of the device other than its
intended use and purpose may result in the manufacturer
refusing to honour warranty claims for product damage. In
this case, liability for consequential damage to persons or
property will also be excluded. Also observe the informa-
tion in the operating instructions for your sun shading
system. The automatic or manual operation of the sun
shading system when iced over as well as using the sun
shading system during severe weather may cause dam-
age and must be prevented by the user through suitable
precautions.
Obligations for the disposal of electrical devices
A marking with this symbol indicates the following
obligations under the scope of legal regulations:
The owner of this electrical device must dispose of it
separately from unsorted municipal waste for further
recycling.
Used batteries and accumulators that are not enclosed
in the old device, as well as lamps/bulbs that can be
removed from the old device without breaking, must be
disposed of separately.
Distributors of electrical devices and disposal companies
are obliged to take back the equipment free of charge.
The owner must take it upon themselves to delete any
personal data contained in the electrical device prior to
disposal.
Technical data
GA Standard
min.
typ.
max.
Unit
Supply 230 V AC
operating voltage
207
230
253
V AC
power consumption
5
80
VA
Output
Control voltage
22
29
32
V DC
Current
(all 4 facades)
2
A
Input (central / local)
Input voltage inactive
0
0
2
V DC
Input voltage active
17
24
32
V DC
Input current active
13
mA
Housing
Dimensions L x W x H
240 x 160 x 90 mm
degree of protection
IP 54
Connection
All connections
screw terminals
Connection terminals
supply line
0,5...1,5 mm
2
control line,
push button line
0,5...1,5 mm
2
Miscellaneous
Conformity
can be viewed at
This device complies with the EMC directives for use in re-
sidential and commercial areas.
Ambient conditions
Operating temperature
0
40
°C
Storage temperature
-25
75
°C
Humidity
(not condensing)
10
40
80
%H
rel
Degree of soiling
2
Article number
Floor distribution control
Standard (GA) Standard
for 4 facades
1002 253
WAREMA Renkhoff SE
Hans-Wilhelm-Renkhhoff-Strasse 2
97828 Marktheidenfeld, Germany