background image

3

warema_866217_alhb_en_v6•2022-07-01

We reserve the right to make technical modifications

240

160

M25

M25

M20

8 pcs. Plug (step support) M20

90

228.5

130.5

Mounting holes Ø 4 mm

Fig. 2 

Dimensional drawing

control

Facade 2

E

12

0

P

P

UP

DOWN

+24V

(2Res.)

Control line

0 0 +  + 

Central control

YR 6x0.8mmø 

 0V

Kompakt 

MSE 

Standard

MSE 

0

E

0

E

P

(2Res.)

YR 6x0.8mmø 

Control line

Central control

AS4

MSE 

0

0

P

UP

(2Res.)

DOWN

YR 6x0.8mmø 

 

±

0V

+24V

Control line

Central control

DOWN

single

UP

0V

13 14 15 16

Facade 3

control

P

0

12 13 14

E

16

15

12

P

Facade 4

14

16

15

13

0

E

control

0

+  + 

0

DOWN

+24V

UP

 

±

0V

Central control
Control line

(2Res.)

YR 6x0.8mmø 

Piccolo M230

MSE 

14

control

P

0

12 13

E

Facade 1

15 16

The maximum current carrying capacity of the floor control distribution board amounts to 2 A. The following current values have to be taken into consideration when calculating the maximum

number of motor control units that can be connected to a floor control distribution board: per MCU Standard       

per MCU Piccolo 

100 mA has to be deducted at the first floor control distribution board for each further GA unit.

25mA => corresponds to 80 MCUs per floor control distribution board

per MCU Arbeitsstellung

25mA => corresponds to 80 MCUs per floor control distribution board

25mA => corresponds to 80 MCUs per floor control distribution board

At a MCU Compact a maximum of 200 MCU may be connected to the floor control distribution board.

The specified number of units has been calculated without consideration of the voltage drop. Please observe the corresponding voltage drop diagrams in this respect.

Fig. 3 

Terminal diagram GA to MCU

Отзывы: