3
warema_866217_alhb_en_v6•2022-07-01
We reserve the right to make technical modifications
240
160
M25
M25
M20
8 pcs. Plug (step support) M20
90
228.5
130.5
Mounting holes Ø 4 mm
Fig. 2
Dimensional drawing
control
Facade 2
E
12
0
P
P
UP
DOWN
+24V
(2Res.)
Control line
0 0 + +
Central control
YR 6x0.8mmø
0V
Kompakt
MSE
Standard
MSE
0
E
0
E
P
(2Res.)
YR 6x0.8mmø
Control line
Central control
AS4
MSE
0
+
0
+
P
UP
(2Res.)
DOWN
YR 6x0.8mmø
±
0V
+24V
Control line
Central control
DOWN
single
UP
0V
13 14 15 16
Facade 3
control
P
0
12 13 14
E
16
15
12
P
Facade 4
14
16
15
13
0
E
control
0
+ +
0
DOWN
+24V
UP
±
0V
Central control
Control line
(2Res.)
YR 6x0.8mmø
Piccolo M230
MSE
14
control
P
0
12 13
E
Facade 1
15 16
The maximum current carrying capacity of the floor control distribution board amounts to 2 A. The following current values have to be taken into consideration when calculating the maximum
number of motor control units that can be connected to a floor control distribution board: per MCU Standard
per MCU Piccolo
100 mA has to be deducted at the first floor control distribution board for each further GA unit.
25mA => corresponds to 80 MCUs per floor control distribution board
per MCU Arbeitsstellung
25mA => corresponds to 80 MCUs per floor control distribution board
25mA => corresponds to 80 MCUs per floor control distribution board
At a MCU Compact a maximum of 200 MCU may be connected to the floor control distribution board.
The specified number of units has been calculated without consideration of the voltage drop. Please observe the corresponding voltage drop diagrams in this respect.
Fig. 3
Terminal diagram GA to MCU