68
Technical Data
Working temperature range:
0°C - 52°C
above an ambient temperature of 42°C the permis-
sible switching current is reduced (see Derating)
Storage temperature range:
-25°C - 70°C
Relative humidity:
5..95% rH
(non-condensing)
Pollution degree:
2
Operating altitude:
0 .. 2000m above sea level
Ventilation:
No external ventilation required
Electrical data
Supply voltage:
110 - 230V AC, 50/60Hz
Current draw:
150 - 50 mA
Over-voltage category:
Category II
Protection class:
I
Galvanic isolation:
Digital output - Network: min. 2000 V
Digital input - Network: min. 2000 V
Digital outputs:
One relay potential-free contact
AC1: 16 A / 250 V AC
AC15: 3 A / 120 V 1.5 A / 240 V
AC3: 750 W
DC1: 16 A / 24 V DC
DC13: 0.22 A / 120 V 0.1 A / 250 V
max. 1800 switching cycles per hour
Digital inputs:
One digital input,
max. input voltage 250V AC 50/60Hz
Switching threshold 80V +/- 10V
Integrated 32-bit pulse counter
Network:
10/100BaseT autosensing
Connections
Network:
RJ45
IO and power:
8x screw terminal, 5mm spacing
Connectable wires:
Solid conductor: 0.2 – 4,0 mm2
Stranded: 0.2 – 2.5 mm2
Lead with end ferrule: 0.25 – 2.5 mm2
Only one conductor per clamp!
Screw tightening torque:
0,5 .. 0,6 Nm
Displays
LED:
Power
Network status
Digital I/O states
Data transmission: