22
Installation and Wiring
Installation #57838
Installation of the Web-IO 4.0 Digital 230V Relais 4xNO, 4xCO,
must for reasons of contact protection be in an enclosed
housing, a sub-distribution unit or a control cabinet. The
108mm (6 TE) wide device is then fastened to a 35mm DIN rail.
Wiring #57838
The supply voltage is connected to the Web-IO 4.0 #57838 via
the 3-pole, pluggable screw terminal.
The device provides two green, 11-pin, pluggable screw
terminals for connecting the outputs. Solid wire or stranded
wire with a maximum cross-section of 2.5qmm may be used
for the wiring.
Please use a 3mm flat screwdriver to tighten the terminal
screws. Do not exceed a tightening torque of 0.6 Nm.
Connecting the supply voltage
The Web-IO 4.0 can be operated at an AC voltage of between
110V and 230V and a frequency between 50 and 60Hz. The
Power LED indicates the presence of supply voltage.
L1
N
PE
W&T
www.WuT.de
Error
Power
Status
Reset
Web-IO #57732
N
L1
IN
OUT
16A
http:// . . .
1x 110-230V~ In, 1x Relais
110-230V~
50/60Hz
50-150mA
Max.
250V~
Out 4
Out 5
Out 0
Out 1
Wiesemann&Theis GmbH
Porschestraße 12
42279 Wuppertal
Power
Out 6
Out 7
Out 2
Out 3
Status
Warning
Error
Reset
L1
N
#57838
230V Relais, 4xNO, 4xCO
Web-IO 4.0
110-230V~
50/60Hz
50-150mA
Outputs
max. 8x6A
http:// ____ . ____ . ____ . ____
W&T
www.WuT.de