translating the .txt Profile
When opened in a terminal program or text editor, the Lifeline Standard AGM program
will appear as follows:
#
# LIFELINE AGM config file
#
#
Based on details in: Lifeline Technical Manual, rev E
#
#
Date: 3/17/2020
#
#
Lifeline standard
#
100c alternator
#
# Lifeline AGM
$SCA: 0,100,1.00,0.75,0.50,0,0,0,10000,0,0,30,0@
$CPA:7 14.3,360,3,0@
$CPO:7 0, 0, 0.0, 0@
$CPF:7 13.3, -1, 0, 0, -50, 12.5, 0@
$CPE:7 15.5,25,600,0@
$CPP:7 0,0.0,0,0.0@
$CPB:7 0.022, -30, -40, 71, 0.0, -99, -99, 15, 2000@
$SCN: 0,Lifeline,1234@
$SCO: 0,0,0,0@
Each line of the .txt file provides commands and values specific to various aspects
of the charge program. The first line of code, designated as $SCA, changes the
parameters of the alternator in the table of system configurations. Meanings for the
values are as follows (note that values are deliniated by commas):
$SCA:
0
,
100
,
1.00
,0.75,0.50,0,0,0,10000,0,0,
30
,0@
1
2
3
4
5
6
7
8
9 10 11
12
13
1. factory use only
2. alternator target temperature (°c) – Temperature regulator will attempt to maintain at
alternator temperature sensor. Contact your alternator manufacturer for recommended
temperature setting and sensor location. For added system safety, consider setting your
value 10-20 degrees below the manufacturer’s recommendation.
3. alternator derate (normal) – When no derate modes are selected.
4. alternator derate (small alternator mode) – When DIP Switch #8 is selected.
5. alternator derate (half output) – Selected when alternator temperature sensor wires
are shorted.
6. Pull Back factor (PBf) – Reduces field at idle (Set “0” to disable) (Set “1” to enable).
7. amp cap – (-1
500) Allows maximum amperage limit if current shunt is connected.
8. system watts cap – (-1
20000) Limits maximum wattage.
9. amp shunt ratio – Indicates the current shunt’s ratio (Amps/mVolts) Default setting is
for a 500A/50mV shunt (500/0.050=10000)
p
a
ge 8
iMportant: the following information is provided for reference, and is intended
to provide guidance required to tailor the configuration profile to your system.
Commonly adjusted settings are highlighted in
red
. please refer to the Wakespeed
Communications and Configuration guide for detailed configuration instructions.