The sixth line of code, designated as $CPP, updates the parameters of the Post 

Float portion of the charge profile. Meanings for the values are as follows (note that 

values are deliniated by commas): 

$CPP: 

7,0,0.0, 0, 0.0@

1

2

3

5

4

1.  charge Profile table entry – Identifies the Profile number being modified by the new 

configuration. Select 7 or 8.

2.  exit duration – Whole number (0 

 30000 (500 hours) controls timer duration once 

post float stage is entered. When the end of the timed period is reached, the regulator 

will loop back to bulk mode. Zero value will cause regulator to remain in Post Float until 

triggered by another exit criteria.

3.  revert VBat – Floating point number (0.0 to 20.0) designates the minimum Post Float 

voltage, below which the regulator will be triggered to return to bulk mode. O.O setting 

disables this feature.

4.  revert amp-hours – Whole number (-250 to 0) determines the accumulated number of 

amp-hours removed during Post Float which will cause the regulator to return to re-start a 

charge cycle and return to bulk mode. Setting the value at zero will disable this function.

5.  VBat set Point – Floating point number (0.0 to 20.0) designates the target voltage used 

during Post Float mode. Setting at 0.0 will disable charging during Post Float mode.

The seventh line of code, designated as $CPB, updates the battery parameters of 

the regulator’s charge profile. Meanings for the values are as follows (note that values 

are deliniated by commas): 

$CPB: 7,0.022,-30, -40, 71, 0.0, -99, -99, 15, 0.0@

1

2

7

8

9

10

6

5

4

3

1.  charge Profile table entry – Identifies the Profile number being modified by the new 

configuration. Select 7 or 8.

2.  VBat compensation – Floating point value (0.0 

 0.1) adjusts a VBat voltages based 

on measured battery temperature. Normalized 12V system with zero correction at 

25°C. “0.0” will disable temperature-based voltage compensation.

3.  minimum compensated temperature – Whole number (-40 

 40). Additional volt-

age compensation will be discontinued when measured battery temperature is below 

value chosen. Measured in °C.

4.  minimum charge temperature – Whole number (-50 

 10). Charging will be discon-

tinued when measured battery temperature is below value chosen. Measured in °C.

4.  exit duration – Whole number (0 

 600 (10 hours) controls duration regulator will 

remain in equalization mode, at which point the regulator  will return to float voltage. “0” 

will disable this feature.

5.  exit amps – Whole number (0 

 50) Controls minimum delivered current level before 

regulator exits equalization to float. “0” will disable this feature. Note: operator is re-

quired to ensure that engine is kept at sufficient RPM to enable delivery of necessary 

current to complete equalization, prior to returning to float mode.

p

a

ge 

11 

 

Содержание WS500

Страница 1: ...d a Micro USB cable these configuration files are downloadable from the Wakespeed website and uploaded to the WS500 Regulator Configuring the regulator does not require that the WS500 is installed in...

Страница 2: ...hnical page www wakespeed com technical html Under the table header WS500 Configuration Files is a list of available files broken down by manufacturer and product series When the desired battery profi...

Страница 3: ...configuration profile is found on the Wakespeed website and is downloaded to your computer it should be placed on the computer s desktop Depending on the Windows system being used double click the ZI...

Страница 4: ...ting tha Windows is not allowing the batch file to be opened This can be overridden by clicking the More info link and clicking on the Run anyway button on the next window 2 A new window will open on...

Страница 5: ...cessfully loaded and verified press and release the regulator s reset button 9 Count to five then press any key on the computer s keyboard to load the configuration file for your battery type 10 As sh...

Страница 6: ...warm up delay The percentage of alternator de rate The actual capacity of the batteries being charged Accessing the Configuration file Within the ZIP file is the folder containing the data and Wakesp...

Страница 7: ...not familiar with this process Failure to properly follow guidelines may void your warranty and damage your system The configuration file broken down in the next several pages is intended to provide a...

Страница 8: ...lator will attempt to maintain at alternator temperature sensor Contact your alternator manufacturer for recommended temperature setting and sensor location For added system safety consider setting yo...

Страница 9: ...0 3 0 CPO 7 0 0 0 0 0 1 1 2 2 3 3 4 4 5 5 1 Charge Profile Table Entry Identifies the Profile number being modified by the new configuration Select 7 or 8 2 VBat Set Point Identifies the voltage set p...

Страница 10: ...ing float the delivered amps will be monitored and regulate to the value set Range is 0 50 Zero setting will disable over charge mode 4 Exit Duration Whole number 0 30000 controls timer duration once...

Страница 11: ...loat mode The seventh line of code designated as CPB updates the battery parameters of the regulator s charge profile Meanings for the values are as follows note that values are deliniated by commas C...

Страница 12: ...the normalized value As an example if the battery capacity is 750 amp hours the BC Index should be set at 1 5 5 Maximum Charge Temperature Whole number 20 95 Charging will be discon tinued when measur...

Страница 13: ...system voltage detect 4 Lockout Whole number 0 2 Restricts the ability to perform changes and or pro vide input to the regulator which can impact how the alternator charges the batteries Zero setting...

Отзывы: