11.3.3
"I&M0" record
The "Identification and Maintenance" (I&M) independent of the manufacturer
according to the "PROFIBUS Identification & Maintenance Guideline" and are
uniformly defined records for unique device identification. A record contains 64
bytes.
The I/O module supports the I&M0 record for identification purposes as an
electronic type plate. Only read access is possible.
The following table provides an overview of the I&M0 record.
Table 105: I&M0 record, structure
Parameter
Data type
Contents
Description
Manufacturer ID
UNSIGNED16
011D
hex
Unique
manufacturer
ID (specified by the
PNO*)
Order ID
STRING[20]
Order ID
Serial Number
STRING[16]
Serial number of the
I/O module
Hardware Revision
UNSIGNED16
Hardware version
number
Software Revision
UNSIGNED8[4]
See the following
section
Software version
number
Revision Counter
UNSIGNED16
0
Not used
Profile ID
UNSIGNED16
4E00
hex
IO-Link
Profile Specific Type
UNSIGNED16
0005
hex
Interface
Module
I&M Version
UNSIGNED8[2]
01
hex
01
hex
(v1.1)
I&M version
I&M supported
UNSIGNED16
001F
hex
I&M
supported
* PROFIBUS User Organization
More information about "Identification & Maintenance Functions"!
More information about "Identification & Maintenance Functions" is available on
the Internet in the document "Profile Guideline Part 1: Identification &
Technology
PROFIBUS.
11.3.3.1 Order ID
The "Order ID" provides the order number of the I/O module as an ASCII string.
Unused data bytes are populated with "0x20".
Example article number of the IO-Link master: 750-657