110 Appendix
WAGO-I/O-SYSTEM
750
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
The fields within the structure mean the following:
Table 82: MASTER_MIN_CYCL, structure description
Bit
Value
(hex)
Value
(time)
Calculation of the
Master Cycle Time
0
0,1 ms 0 ms + MULTIPLIER * TIMEBASE
1
0,4 ms 6,4 ms + MULTIPLIER * TIMEBASE
TIMEBASE
2
1,6 ms 32,0 ms + MULTIPLIER * TIMEBASE
MULTIPLIER
Var. Multiplier for master cycle time
11.3.1.4 IOL_REV
The IOL_REV data field provides the version of the IO-Link specification
supported by the I/O module. A value of 0x11 means IO-Link Revision 1.1.
Table 83: IOL-M Basic Configuration, IOL_REV
Name
Data type
Access
Value
IOL_REV UNSIGNED8 ro
0x11
The following table provides an overview of the data structure.
Table 84: COM_MODE, Data structure
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
IOL_REV
Table 85: COM_MODE, Description
Bit field
Access
Value
Description
0x10
IO-Link master according to IO-Link specification v1.0
IOL_REV
ro
0x11
IO-Link master according to IO-Link specification v1.1
11.3.1.5 IOLM_FEATURE
The IOLM_FEATURE data field contains various control bits for configuring the
IO-Link master.
Table 86: IOL-M Basic Configuration, IOLM_FEATURE
Name
Data type
Access
Value
IOLM_FEAT UNSIGNED16
r/w
Var.