86
Diagnostics
WAGO-SPEEDWAY 767
767-5803/000-800 8DIO 24V DC 0.5A IF (8xM12)
Manual
Version 1.1.0
Table 52: Operating messages 1
Pos. LED Color/Status
Cause
Remedy/information
15
SB
Green and orange,
flashing, 1 Hz
The set substitute value is
applied to the module.
Can be set by the fieldbus
coupler if fieldbus is missing.
Check the fieldbus connection
and the status of the higher-
level controller.
Orange, flashing,
2 Hz
The module has detected the
S-BUS.
-
Orange and green,
flashing, 4 Hz
The last module is being
detected in the 767 node.
Check the S-BUS terminator
and/or the S-BUS cables.
Orange, flashing,
1 Hz
The fieldbus coupler is
addressing the module in the
767 node.
-
Orange and green,
flashing, 2 Hz
The S-BUS parameters are
being stored by the fieldbus
coupler.
-
Orange
The firmware is being
updated.
All 767 Series components
are being updated by the
fieldbus coupler within the
node.
Orange, flashing,
4 Hz
The module is attempting to
establish communication with
the fieldbus coupler.
Check the power supply to
upstream 767 Series
component and/or check the
S-BUS cable for damages.
Pos: 43.5 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen 767- 5xxx D IO Allgemein ( Pos. 15, T eil 2) @ 7\mod_1268637618295_21.docx @ 52466 @ @ 1
15
SB
Green, flashing,
1 Hz
The module is in HOLD
mode.
Is initiated by the fieldbus
coupler. In DI mode, the last
input values transferred to the
fieldbus coupler are kept in
the process image. In DO
mode, the last output values
are retained.
Green, flashing,
2 Hz
The module is in STOP
mode.
Is initiated by the fieldbus
coupler. In DI mode, the input
values are set to 0 in the
process image. In DO mode,
the output value is output as 0.
Pos: 43.6 /Dokumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1