60
Parameterizing
WAGO-SPEEDWAY 767
767-5803/000-800 8DIO 24V DC 0.5A IF (8xM12)
Manual
Version 1.1.0
Table 33: Overview of adjustable parameters for the digital outputs
Parameter
Description
Actuator restart mode
Set the restart behavior of an enabled output if the output has been
disabled due to the "Overtemperature" diagnosis. You have the following
options:
Delayed*
After the time set has elapsed ("Restart delay, actuator"), the output is
switched on again automatically.
Diagnostic acknowledge
The output is only switched on after acknowledging the diagnostic
message. Acknowledge the diagnostic message from the higher-level
controller or PLC. The respective coupler manual specifies which fieldbus
couplers this functionality supports.
Information about diagnostic acknowledgement:
When using fieldbus couplers that do not support the
diagnostic acknowledgement, disabled outputs may remain
OFF.
Restart delay actuator
Time in 100 ms intervals after which an off output is automatically
restarted in case of error.
You must unselect the checkbox under "Restart mode actuator" (0).
Default setting: 10
Note
If you set the time of the "Restart delay actuator" parameter
to 0 ms, the I/O LED appears yellow rather than red in case
of a short circuit or overload due to the short restart interval
(see section "Diagnostics").
Overtemperature
The module has identified a overtemperature on the corresponding
channel (1 – 8) (only enabled when the actuator output is switched on).
* Default status
**
The last value is the value output to the contact before occurrence of the respective interruption.
This can be, for example, a process value or manual operation value.