Analog Inputs 750-452, 454,482,484
:$*2
Ç
,
2
Ç
6<67(0
5
Input current
0-20 mA
Binary value
X : without meaning
F : short circuit
open circuit
Ü : overflow
X F Ü
Hex.
Dec.
> 20
0100 0000 0000 0
0 0 1
40 01
16385
20
0100 0000 0000 0
0 0 0
40 00
16384
10
0010 0000 0000 0
0 0 0
20 00
8192
5
0001 0000 0000 0
0 0 0
10 00
4096
2.5
0000 1000 0000 0
0 0 0
08 00
2048
1.25
0000 0100 0000 0
0 0 0
04 00
1024
0.625
0000 0010 0000 0
0 0 0
02 00
512
0.0976
0000 0000 0000 1
0 0 0
00 08
8
0
0000 0000 0000 0
0 0 0
00 00
0