SSI encoder 750-630
:$*2
Ç
,
2
Ç
6<67(0
2
Technical Data:
Series 750
630
630/000-001
630/000-006
Encoder connections
Data Input: D+; D-; Clock Output: CI+; CI-
Current consumption
(internal)
85mA typ.
Power supply
24V DC (-15%/+20%)
Sensor power supply
24V DC via power jumper contacts
Baud rate
max. 1 MHz
Data field width
32 Bit
Signal output (clock)
differential RS 422
Signal input (positional)
differential RS 422
Output data format
Graycode / Dualcode
Bit width
32 Bit: Data; 8 Bit: Control/Status
Configuration
none, optional via software parameter
Signal isolation
500 V system/power supply
Temperature range
0°C....+55°C
Wire connection
CAGE CLAMP; 0.08 x 2.5mm
2
AWG 28-14
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
Default Configuration
125 kHz
125 kHz
250 kHz
Graycode
Binary
Graycode
24 Bit Data
Resolution
24 Bit Data
Resolution
24 Bit Data
Resolution