Input for thermocouple modules 750-462,469
:$*2
Ç
,
2
Ç
6<67(0
3
Temperature Ranges of the connectable sensors:
L
-25°C....+900°C
K
-100°C...1370°C (Default)
J
-100°C...+1200°C
750-462/000-006
750-469/000-006
E
-100°C...1000°C
750-462/000-008
750-469/000-008
T
-100°C...+400°C
750-462/000-002
750-469/000-002
N
-100°C...+1300°C
750-462/000-009
750-469/000-009
U
-25°C...+600°C
750-462/000-011
750-469/000-011
B
600°C...+1800°C
750-462/000-007
750-469/000-007
R
0°C...+1700°C
750-462/000-010
750-469/000-010
S
0°C...+1700°C
750-462/000-001
750-469/000-001
mV-Meter
-120 mV...+120 mV
750-462/000-003
750-469/000-003
Table 1: Temperature ranges
of the connectable sensors
Attention: The range of the mV Meter is 0 to 120mV at the moment!
LED functions:
green LED: Function
ON: Normal
OFF: Watchdog-Timer Overflow
If the PLC does not transmit processing data for 100 ms the green LED
stops lightning.
red LED: Error
ON: Over- or underrange or broken wire (bei 750-469)
OFF: voltage is in the measuring range