751-4001 [AS-Interface Module 4OUT 24V/2A Single]
•
9
Connectors
WAGO-I/O-SYSTEM 751
AS-Interface Components IP67
2.1.1.3 Connectors
2.1.1.3.1 AS-Interface Cable and AUX Cable
The AS Interface cable and the AUX cable are connected using piercing
technology.
When assembling the upper part, contacts are pressed into the cable which is
located in the ground plate, making the electrical contact.
The functional earth contact is also made during assembly of the upper part.
2.1.1.3.2 Actuator Connectors
Actuator connections are 5-pole sockets for M12x1 round plugs.
When using angled connectors, the socket design provides a connecting angle
of 45° (top left or top right) for the connecting cable.
The following table shows the pin assignment of the sockets.
Tab. 2.1.1-1: Actuator Connector
Actuator Connectors
Connector
Pin Function
--- ---
1
not
used
--- ---
2
not
used
OUT 1/3 OUT 2/4
3
External voltage –
OUT 1/3 OUT 2/4
4
Switching
3
4
2
1
3
4
2
1
5
5
OUT 1/3
OUT 2/4
Fig. 2.1.1-2: Actuator
Connector
gqxxx02x
OUT 1/3 OUT 2/4
5
Functional earth FE
Pin 5 of the sockets makes connection to functional earth. Four-pole plugs
without functional earth or 5-pole plugs with functional earth may be
connected.
Warning
Unused actuator connections must be sealed with protective caps!
2.1.1.3.3 Programming Connector
The PGM connection is the programming connector. It is a plug for a DC
socket which is compatible with all popular programming adapters, for
example Fuchs VAZ-PK-1.5M-V1-G.
Please note manufacturer documentation for the operation of the programming
device.