298 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Instance 766 ... 1020 (Digital Output value 766 up to 1020)
Table 251: Discrete Output Point Extended 3 (72
hex
) – Instance 766...1020
Attribute ID Access Name
Data type Description
Default
value
1
Get
DopObj_Value BYTE
Digital Output
(only Bit 0 valid)
-
Common Services
Table 252: Discrete Output Point Extended 2 (6E
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
12.3.5.21 Analog Input Point (67
hex
)
This class enables the reading of data of a particular analog input point (AIP). An
analog input point is part of an analog input module.
Instance 0 (Class Attributes)
Table 253: Analog Input Point (67
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1 ... 255 (Analog input 1 up to 255)
Table 254: Analog Input Point (67
hex
) – Instance 1 ... 255
Attribute ID Access Name
Data type Description
Default
value
1
Get
AipObj_Value
ARRAY of
BYTE
Analog Input
-
2
Get
AipObj_Value_L
ength
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 255: Analog Input Point (67
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute