WAGO-I/O-SYSTEM 750
Fieldbus Communication 257
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Table 155: Register address 0x1032
Register address 0x1032 (4146
dec
) with a word count of 3
Value
Value
Access
Access
Description
Description
Table 156: Register Address 0x1035
Register address 0x1035 (4149
dez
) 1 word
Value
Configuration of the time offsets to the GMT time
Access
Read/write
Default
0x0000
Description
Register to set the time offset to the
UTC time (Greenwich meridian) with a possible
setting range from -12 to +12.
Table 157: Register Address 0x1036
Register address 0x1036 (4150
dez
) 1 word
Value
Configuration of summer or winter time
Access
Read/write
Default
0x0000
Description
Register to set winter or summer time (Daylight Saving Time).
The values 0 and 1 are valid.
Table 158: Register Address 0x1037
Register address 0x1037 (4151
dez
) with a word count of 3
Value
Configuration of Modbus Response Delay Time
Access
Read/write
Default
0x0000
Description
This register saves the value for the Modbus Response Delay Time for a Modbus
connection. The time base is 1 ms. On the Modbus TCP connection, the
response will be delayed by the inscribed time.
Table 159: Register Address 0x1050
Register address 0x1050 (4176
dec
) with a word count of 3
Value
Diagnosis of the connected I/O modules
Access
Read
Description
Diagnosis of the connected I/O modules, length 3 words
Word 1: Number of the module
Word 2: Number of the channel
Word 3: Diagnosis