Device Description 15
787-2861 Electronic Circuit Breaker
Manual
Version 1.3.1
Pos: 18 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/Gerätebeschr eibung - Ü berschrift 1 @ 3\mod_1233756084656_21.docx @ 27096 @ 1 @ 1
3
Device Description
Pos: 19.1 /Serie 787 (EPSITRON)/Ger ätebeschrei bung/Beschr eibung/Anwendung/Anwendung 787-2861 @ 23\mod_1435323488284_21.docx @ 184666 @ @ 1
The 787-2861/0xx0-0000 electronic circuit breaker reliably protects load circuits
against short circuiting and overloading. The 24 VDC input voltage can be
provided with fuse protection for the following current values:
Table 4: Output Fuse Protection
Version
Fuse Protection
Color Coding
787-2861/0050-0000
0.5 A
Green
787-2861/0100-0000
1 A
Brown
787-2861/0200-0000
2 A
Red
787-2861/0400-0000
4 A
Yellow
787-2861/0600-0000
6 A
Blue
787-2861/0800-0000
8 A
Gray
787-2861/0108-0020
1 A ... 8 A
-
The electronics can accommodate brief current peaks.
Pos: 19.2 /Serie 787 (EPSITRON)/Ger ätebeschrei bung/Beschr eibung/LED-Anzeig e/LED-Anzeige 787- 2861 @ 23\mod_1436342089493_21.docx @ 185670 @ @ 1
LEDs indicate the respective status of the output and current setting.
Pos: 19.3 /Serie 787 (EPSITRON)/Ger ätebeschrei bung/Beschr eibung/Funkti on/Funktion 787-2861: Kurzschluss und Ü berlast @ 23\mod_1436342179935_21.docx @ 185687 @ @ 1
In the event of a short circuit or overloading, the individual channel is de-
energized after a defined trip time.
Pos: 19.4 /Serie 787 (EPSITRON)/Ger ätebeschrei bung/Beschr eibung/Anwendung/Hinweise/Hinweis: Ther mische Entspannung abwarten 787- 16xx @ 12\mod_1342431732847_21.docx @ 100298 @ @ 1
Wait for temperature to return to normal!
If a channel has been de-activated due to short-circuiting or overloading, wait
until the temperature returns to its normal range (cooling period) before re-
activating the channel.
Pos: 19.5 /Serie 787 (EPSITRON)/Ger ätebeschrei bung/Beschr eibung/Funkti on/Funktion 787-2861: Sig nal kontakte @ 23\mod_1435572867601_21.docx @ 184762 @ @ 1
The device has a control input and a signal output.
•
Control input:
The channel can be switched ON and OFF from here.
•
Signal output:
The operating status can be read from here.
Pos: 19.6 /Serie 787 (EPSITRON)/Ger ätebeschrei bung/Beschr eibung/Anwendung/Anwendung 787-2861/0108- 0020 @ 28\mod_1484046480599_21.docx @ 402718 @ @ 1
The 787-2861/0108-0020 electronic circuit breaker variably protects load circuits
with current levels from 1 A … 8 A. The trip current and behavior of the signal
output can be configured using the push and slide switch. LEDs indicate the
respective status of the channel and current setting.