38 Connect Devices
787-2861 Electronic Circuit Breaker
Manual
Version 1.3.1
Pos: 65 /Serie 787 (EPSITRON)/Anschließ en/Potential verteilen 787-2861 @ 25\mod_1456309570497_21.docx @ 202387 @ 2 @ 1
6.2
Distribute Potential
The devices have two connection points for the positive output
(connections 6 and 7) and two connection points for the negative input/output
(connections 4 and 8).
Once the device is powered by a push-in type jumper bar, two load circuits can
be connected to the device directly (V
OUT
+/GND). Additional terminal blocks can
be omitted.
Observe the following note if you would like to common potentials with relays:
Connected relay: Only common equal potentials!
Damage to the device may occur if different potentials are commoned! If you use
the 857-304 relay, the potentials must only be commoned via the connections
VIN+ (connection 3) and GND (connection 8)!
Pos: 66 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1