WAGO-SPEEDWAY 767
Diagnostics
65
767-6402 4 AI RTD
Manual
Version 3.1.0
Table 32: Operating messages 1
Pos. LED Color/Status
Cause
Remedy/information
15
SB
Green and orange,
flashing, 1 Hz
The set substitute value is
applied to the module.
Can be set by the fieldbus
coupler if fieldbus is missing.
Check the fieldbus connection
and the status of the higher-
level controller.
Orange, flashing,
2 Hz
The module has detected the
S-BUS.
-
Orange and green,
flashing, 4 Hz
The last module is being
detected in the 767 node.
Check the S-BUS terminator
and/or the S-BUS cables.
Orange, flashing,
1 Hz
The fieldbus coupler is
addressing the module in the
767 node.
-
Orange and green,
flashing, 2 Hz
The S-BUS parameters are
being stored by the fieldbus
coupler.
-
Orange
The firmware is being
updated.
All 767 Series components
are being updated by the
fieldbus coupler within the
node.
Orange, flashing,
4 Hz
The module is attempting to
establish communication with
the fieldbus coupler.
Check the power supply to
upstream 767 Series
component and/or check the
S-BUS cable for damages.
Pos: 41.5 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen 767- xxxx DI/AI Allgemein (Pos. 15, T eil 2) @ 7\mod_1268637528606_21.docx @ 52460 @ @ 1
15
SB
Green, flashing,
1 Hz
The module is in HOLD
mode.
Is initiated by the fieldbus
coupler. The last input values
transferred to the fieldbus
coupler are kept in the process
image.
Green, flashing,
2 Hz
The module is in STOP
mode.
Is initiated by the fieldbus
coupler. The input values are
set to 0 in the process image.
Pos: 41.6 /Dokumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1