44
Connecting Data and Supply Cables
WAGO-SPEEDWAY 767
767-6402 4 AI RTD
Manual
Version 3.1.0
Pos: 23.15 /Serie 767 ( WAGO-SPEED WAY)/Anschluss D aten- und Versorgungskabel/I/O-M odule/Anschluss_Spannungsversorgung allgemein @ 5\mod_1249291817750_21.docx @ 39906 @ 2 @ 1
5.4
Connecting the Supply Cable
The supply cable provides power to the module.
Requirement:
The WAGO supply cables K1 and K2, which are pre-assembled on both ends,
must be available (see figure on next page).
The following table outlines the assignment of the supply connections:
Table 20: Supply connection assignment
Connection
Contact
Description
IN
OUT 1
24 VDC U
LS
2
24 VDC U
A
3
0 V U
LS
4
0 V U
A
Pos: 23.16 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sicherheitshinweise/Achtung/Achtung: Höchste Strombel astbar keit der Versorgungskontakte @ 8\mod_1278308653219_21.docx @ 58916 @ @ 1
The highest current carrying capacity of the supply contacts is 4 A!
Always observe the maximum current carrying capacity per supply line (U
LS
, U
A
)
for each 767 Series component and the overall power consumption for all
767 components. Neither of these values shall exceed 4 A since an increase in
current causes the contacts to overheat and damages the 767 Series components.
Information regarding the power demand of each 767 Series component can be
found in the corresponding data sheet, which is available from
www.wago.com
.
Pos: 23.17 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1