Parameterizing
WAGO-SPEEDWAY 767
767-6402 4 AI RTD
Manual
Version 3.1.0
Pos: 30.12 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung 767-6402 Parameter der Eing änge und anwenderdefi nierte M essber eiche @ 5\mod_1249386201671_21.docx @ 40303 @ 22 @ 1
7.3
Analog Inputs
Table 27: Overview of adjustable parameters for the analog inputs
Parameter
Description
Designation
Electronic marking field (max. 40 characters)
Display mode process
value
Selection of the representation for displaying the process value and limit
values:
- Decimal
- Hexadecimal
- Physical
Process image value
An updated measured value for the temperature is displayed here.
If the "Simulation" parameter has been activated, enter the simulation
value here.
Measuring range
Select the measuring range here.
You have the following options:
- Pt 100
- Pt 200
- Pt 500
- Pt 1000
- Ni 100
- Ni 120
- Ni 1000
-
1 kΩ resistance
-
4 kΩ resistance
- Potentiometer %
- User-defined 1
- User-defined 2
- User-defined 3
- User-defined 4
Hinweis
Measuring ranges
The user-defined measuring ranges 1 – 4 can by
configured by you. For more information, see section
"Measurement Range User 1 – 4".
Simulation
If this parameter is activated, you can simulate both the process value
and the channel-specific diagnostics.
Moreover, the input field for the process value is made available so that
you can enter the input value that is to be simulated.
Upper user limit
Here you can enter the limit value that is to trigger a diagnostic when
exceeded.
Lower user limit
Here you can set the limit value that is to trigger a diagnostic when
under-run.
Substitute value
Here you can enter the process value that is transmitted in the case of an
error.
Default
setting: 32767