56
Parameterizing
WAGO-SPEEDWAY 767
767-6402 4 AI RTD
Manual
Version 3.1.0
7.4
Measurement Range User 1 – 4
Table 28: Overview of adjustable parameters for the user-defined measuring ranges
Parameter
Description
Copy presettings from
Here you can select the area from which the settings for this measuring
range should be acquired.
You have the following options:
- Pt 100
- Pt 200
- Pt 500
- Pt 1000
- Ni 100
- Ni 120
- Ni 1000
-
1 kΩ resistance
-
4 kΩ resistance
- Potentiometer %
- User-defined 1
- User-defined 2
- User-defined 3
- User-defined 4
Measuring type
Here you can select the base measuring range of the electronics.
You have the following options:
500 Ω
1 kΩ
2.5 kΩ
5
kΩ
Physical conversion
offset
Offset value for calculating the physical value F(x) from the process
value (x).
F(x) = (x + conversion offset) * conversion multiplier.
Physical conversion
multiplier
Conversion factor (gain) for calculating the physical value F(x) from
the process value (x).
F(x) = (x + conversion offset) * conversion multiplier.
Physical unit string
Display of the physical measured value.
Enable user scaling
Here you can activate and deactivate the user scaling ("User Offset"
and "User Gain").
User offset
Offset value for scaling the process value.
The process value is calculated according to the following formula:
F(x) = (x + user offset) * user gain