Parameterizing
WAGO-SPEEDWAY 767
767-5201 TTL Incremental/SSI Encoder
Manual
Version 1.1.0
7.5.2
Connection Mode "Digital Input"
Table 44: Overview of adjustable parameters for the digital inputs
Parameter
Description:
Function mode
Mode display
Designation
Enter a designation for the connection. Max. 40 characters can be
entered.
Input value
The input status is indicated in this field. When simulation is
selected, the field becomes a checkbox.
Activate the checkbox to simulate the status "1" in the process
image independent of the input.
Signal inverting
You can invert the currently pending signal input here.
Checkbox unselected*:
Input signal is shown in the process image as pending at the input.
Checkbox selected:
Input signal is shown as inverted in the process image.
Filter time
Set the input filter for the measured signals here. You have the
following options:
- Off
- 16 µs
- 65 µs
- 250 µs
- 1 ms
Substitute strategy
This is used, e.g. to output the substitute value or the last output
value in the event of a fieldbus interruption. You have the
following options:
- Set to substitute value
*
- Hold last value**
Substitute value
Enter the process value that is output in case of error. In the case of
an error (fieldbus interruption), this value is used with the "Switch
to Substitute Value" strategy.
Checkbox unselected:
0*
Checkbox selected:
1
Simulation input value
Activate this checkbox to switch input simulation on. The field for
the input value then becomes a checkbox for the simulation value.
* Factory default setting
**
The last value is the value output to the contact prior to the occurrence of the corresponding
error. For example, this can be a process value or "manual operation value".