30
Device Description
WAGO-SPEEDWAY 767
767-5201 TTL Incremental/SSI Encoder
Manual
Version 1.1.0
3.7.12 Configurable Functions of the SSI Encoder Interfaces
Table 19
: Technical data − C
onfigurable functions of the SSI encoder interfaces
Length data range
8 bits … 24 bits (default 13)
Data length of the speed
0 bits … 24 bits (default 12)
Speed suppression by the encoder
Off / On
Bus speed of the SSI bus
62.5 / 125 / 250 / 500 kHz / 1 / 2 MHz
Parity
None / odd / even
Coding
Binary / Gray
Alarm bit evaluation
Off / On
3.7.13 Configurable Functions of the Cam Output
Table 20
: Technical data − C
onfigurable functions of the cam outputs
Cam lower value
Value (INT32)
Cam upper value
Value (INT32)
Cam output
Deactivated / DO 1 … 4
Cam active
Off / On
3.7.14 Configurable Functions of the PWM Outputs
Table 21
: Technical data − C
onfigurable functions of the PWM outputs
Duty cycle
0 … 100 % (default 50 %)
Frequency
100 / 200 / 500 Hz / 1 / 2 / 5 / 10 kHz
Substitute value
0 … 100 % (default 50 %)
Substitute value strategy
Switch substitute value/keep last value
3.7.15 Configurable Functions of the Digital Inputs/Outputs
Table 22
: Technical data − C
onfigurable functions of the digital inputs/outputs
Operating mode (per module)
DO / DI / DIO
Input filter (per channel)
16 / 65 / 250 µs / 1 ms / Out
Inversion (per channel)
On / Off
Substitute value strategy (per
channel)
Switch substitute value / keep last value
Substitute value (per channel)
0 / 1
Manual mode (per channel)
On / Off
Manual mode value (per channel)
0 / 1
Online simulation (by channel)
Lock / Unlock; Simulation value: 0 / 1
Online simulation (per
channel/module)
Diagnostics