765-4102/0100-0000
Commissioning
80
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 47: “Port Mode” Drop-Down Menu: Selecting the Operating Mode for Pin 4 of the Selected IO-Link Port
Selection Option
Explanation
Digital output
The port is operated as a digital output (pin 4 serves a
data line). All elements of the port configuration are ig-
nored except for the input and output data length.
Digital output, static on
The port is operated as a digital output (pin 4 serves a
data line). All elements of the port configuration are ig-
nored except for the input and output data length.
Setting the Filter Time for Digital Inputs
The filter time for the digital inputs can be selected from the “Digital input signal filter”
drop-down menu. You can select from the following values:
• No digital input filter
• 3 ms
• 15 ms
• 20 ms
If the “No digital input filter” option is selected, no filtering occurs.
Configuring Pin 2
The behavior of pin 2 can be selected from the
IQ behavior
drop-down menu. The follow-
ing configuration options exist:
Table 48: IQ Behavior Drop-Down Menu – Configuration of Pin 2
Selection Option
Explanation
Not supported
Pin 2 supplies no output voltage
Power 2
Pin 2 supplies 24 VDC output voltage
Configuring the Device Check for Validation and Backup
Note
In the “IOL Autostart” operating mode (see above), this drop-down menu has no ef-
fect.
The
Validation and backup
drop-down menu can be used to determine whether a vali-
dation (device check) is performed and, if so, at what level (Inspection Level) when a con-
nected device is replaced, and whether or not the stored operating parameters of the old
device are carried over to the new one.
The following table explains the possible values for Inspection Level:
Table 49: Possible Values of the Inspection Level Parameter
Inspection Level
Meaning
NO_CHECK
No device check is performed.
TYPE_COMP
A device check for type compatibility is performed.
For the device check, the actual vendor ID is com-
pared to the vendor ID setting in the configuration, and
the actual device ID is compared to the device ID set-
ting in the configuration.
IDENTICAL
A device check for device identity is performed.
The device check for type compatibility is performed,
and the actual serial number is also compared to the
serial number setting of the configuration.