Connect Devices
WAGO-TO-PASS® 761
761-314 TO-PASS® Mobile, 4 AI
Manual
Version 2.0.0
Pos : 26.18 / Serie 761 (T O-PASS)/Ansc hliessen/ Ansc hluss beispi eleAnschl uss beis pi el 761-1xx/-2xx/-3xx AI/ O U - Ü berschrif t 4 @ 15\ mod_1365075195916_21.doc x @ 116496 @ 4 @ 1
5.2.3.2
Voltage Measurement
Pos : 26.19 / Serie 761 (T O-PASS)/Ansc hliessen/ Ansc hluss beispi eleHi nweis : Spannungs mess ung nur über U/I- Wandler @ 7\ mod_1265647550343_21.doc x @ 50060 @ @ 1
Voltage measurement can only be performed via U/I transformer!
Voltage measurement cannot be performed via multiplier at the analog inputs,
since the internal resistance of the
TO-PASS
®
telecontrol module depends on the
input current.
WAGO 857 Series
JUMPFLEX
Isolation Amplifiers for level conversion may be
used for voltage measurement via
TO-PASS
®
telecontrol modules.
Pos : 26.20 / Serie 761 (T O-PASS)/Ansc hliessen/ Ansc hluss beispi ele/Ansc hlus sbeispi el 761-31x 4AI U - Abbildung @ 15\mod_1365081727789_21.doc x @ 116547 @ @ 1
Figure 17: Connection example for voltage measurement via U/I converter at input AI1