WAGO I/O System 750
List of Figures 23
750-940 EnOcean RS-485 Gateway; 868 MHz
Manual
Version 1.3.0, valid from FW/HW Version 01/01
3.4.1
DIP Switch Settings
The EnOcean Gateway hardware properties are set with the four-position DIP
switch (“DIP2”).
Figure 10: Four-Position DIP Switch (“DIP2”) for Configuring the EnOcean Functions
Table 10: DIP Switch Panel for Configuring the EnOcean Functions
DIP
Switch
Meaning
Function in
ON Position
Function in
OFF Position
1
LED functionality
LED “DS” switched off
LED “DS” switched on *
)
2
Repeater mode
Repeater operation
Protocol selection *
)
3
Antenna type
External antenna active
Internal antenna active *
)
4
Protocol selection
Modbus protocol active
ESP3 protocol active *
)
*
)
Default setting
When the Modbus protocol is selected with the four-position DIP switch (“DIP1”),
other settings for Modbus mode are made with the eight-position DIP switch.
Exception: DIP switch 8 functions for the ESP3 and Modbus
protocols.
Figure 11: Eight-Position DIP Switch (“DIP1”) for Configuring the RS-485 Interface
Table 11: DIP Switch Panel for Configuring the RS-485 Interface
DIP
Switch
Meaning
Function in
ON Position
Function in
OFF Position
1
Address 0
Setting the address LSB
See Table “Bit-Coded
Modbus Address.”
2
Address 1
Setting the address
3
Address 2
Setting the address
4
Address 3
Setting the address MSB
5
Baud rate A
Baud rate setting
See Table “DIP Switch
Positions for Selecting Baud
Rate.”
6
Baud rate B
Baud rate setting
7
Termination
RS-485 termination switched
off
RS-485 termination switched
on *
)
8
BIAS network
Switched on (effective with
ESP3 and Modbus
protocols)
Switched off *
)
(effective with
ESP3 and Modbus
protocols)
*
)
Default setting