120 Commissioning
WAGO-I/O-SYSTEM 750 XTR
750-8212/040-010 PFC200 G2 2ETH M12 RS XTR
Manual
Version 1.0.0, valid from FW version 03.01.07(13)
</dg_
7.7
Initiating Reset Functions
You can initiate various reset functions using the mode selector switch and the
Reset button (RST).
7.7.1
Warm Start Reset
The warm start reset function depends on the activated runtime system
(CODESYS 2 or
e!
RUNTIME
).
7.7.1.1 CODESYS 2 Runtime System
</dg_
The CODESYS 2 application is reset on a warm start reset. This corresponds to
the WAGO I/O PRO IDE “Reset” command.
</dg_
To perform a warm start reset, set the mode selector switch to "Reset" and hold it
there for two to seven seconds.
Execution of the reset is signaled by the red “RUN LED” briefly going out when
the mode selector switch is released.
7.7.1.2
e!RUNTIME
Runtime System
All
e!
RUNTIME
applications are reset with a warm start reset. All global data is
set to its initialization values. This corresponds to the
e!
COCKPIT
IDE “Reset
warm” command.
</dg_
To perform a warm start reset, set the mode selector switch to "Reset" and hold it
there for two to seven seconds.
Execution of the reset is signaled by the red “RUN LED” briefly going out when
the mode selector switch is released.
7.7.2
Cold Start Reset
The cold start reset function depends on the activated runtime system
(CODESYS 2 or
e!
RUNTIME
).
7.7.2.1 CODESYS 2 Runtime System
</dg_
On a cold start reset the CODESYS 2 application is reset and the memory
containing the retain variables is cleared.
This corresponds to the WAGO I/O PRO IDE “Reset (Cold)” command.
</dg_
To perform a cold start reset, set the mode selector switch to “Reset” and hold it
there for more than seven seconds.
Execution of the reset is signaled after seven seconds by the “RUN” LED going
out for an extended period. You can then release the mode selector switch.
7.7.2.2
e!RUNTIME
Runtime System
</dg_